| Plan Review Notes For Permit 06021248 |
| Permit Number |
06021248 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-14 00:00:00 | *** DENIED *** | | | 1) PLEASE SUBMIT MANUAL J CAL'S. FOR | | | SECOND FLOOR ALSO. | | | | | | 2) MANUAL J CAL'S. FOR SYSTEM 2 IS | | | CALCULATED AT 4 1/2 FOOT HIGH CEILINGS, | | | PLEASE CORRECT. | | | | | | 3) ENERGY CALCULATIONS ARE CALLING FOR A | | | 18 KW HEATER IN ONE UNIT, AND ELECTRICAL | | | PLANS ARE SHOWING THE HEATER AT 10 KW, | | | PLEASE CORRECT. | | | | | | 4) PLEASE SHOW ON MECHANICAL PLANS THE | | | A/C EQUIPMENT LISTING WITH ALL PERTINENT | | | INFORMATION. | | | | | | 5) SHOW THE SIZE OF THE SUPPLY AIR DUCT | | | FROM MIXING BOX TO MIXING BOX ON THE | | | FIRST FLOOR. | | | | | | 6) PLEASE SHOW ALL GRILL SIZES ON THE | | | MECHANICAL PLANS. | | | | | | 7) PLEASE SHOW ALL BATHROOM EXHAUST FANS | | | ON THE MECHANICAL PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|