| Plan Review Notes For Permit 06021248 |
| Permit Number |
06021248 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} NO LOAD IS SHOWN FOR THE 100 AMP SUB | | | PANEL. PLEASE SUBMIT PANEL SCHEDULES FOR | | | ALL PANELS SO THAT BRANCH CIRCUIT | | | COMPLIANCE MAY BE REVIEWED. | | | | | | 2} PLEASE LABEL THE ROOMS ON THE | | | ELECTRICAL PLANS. | | | | | | 3} HER BATH REQUIRES A RECEPTACLE AT THE | | | SINK TO COMPLY WITH 210.52(D). | | | | | | 4} BEDROOM #3 NEEDS RECEPTACLES ADDED TO | | | COMPLY WITH 210.52(A)(1)&(2). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|