| Plan Review Notes For Permit 06021241 |
| Permit Number |
06021241 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-03 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT. | | | | | | 2) ENERGY CAL'S. ARE CALLING FOR 62,000 | | | TOTAL BTU'S, PLANS ARE CALLING FOR | | | 66,000 TOTAL BTU'S. THE PLANS CAN NOT | | | CALL FOR MORE BTU'S THAN THE ENERGY | | | CAL'S, PLEASE CORRECT. | | | | | | 3) PLEASE NOTE THAT THE SECOND FLOOR, | | | PLAN IS FLIPED. | | | | | | 4) PLEASE SHOW THE DUCT (FLEX) SIZES FOR | | | BEDROOM #2 AND #3. | | | | | | 5) PLEASE SHOW THE HEATER SIZE FOR AHU | | | #2, COPPER LINE SIZES, AND CONDENSATE | | | DRAIN LINE LOCATIONS FOR BOLTH SYSTEMS. | | | | | | 6) PLEASE SHOW ON ALL SHEETS JOB | | | ADDRESS, COMPANY INFOMATION WITH PHONE | | | NUMBER, AND LICENSE NUMBER. | | | | | | 7)ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | 8)CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY. PER 2004 FBC 106.1.1 | | | . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|