2006-03-14 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 225.31 DISCONNECTING MEANS.
 MEANS SHALL BE PROVIDED FOR
 DISCONNECTING ALL UNGROUNDED CONDUCTORS
 THAT SUPPLY OR PASS THROUGH THE BUILDING
 OR STRUCTURE. SHOW LOCATION ON PLAN.
  
 2} 250.32 TWO OR MORE BUILDINGS OR
 STRUCTURES SUPPLIED FROM A COMMON
 SERVICE.
 (A) GROUNDING ELECTRODE. WHERE TWO OR
 MORE BUILDINGS OR STRUCTURES ARE
 SUPPLIED FROM A COMMON AC SERVICE BY A
 FEEDER(S) OR BRANCH CIRCUIT(S), THE
 GROUNDING ELECTRODE(S) REQUIRED IN PART
 III OF THIS ARTICLE AT EACH BUILDING OR
 STRUCTURE SHALL BE CONNECTED IN THE
 MANNER SPECIFIED IN 250.32(B) OR (C).
 WHERE THERE ARE NO EXISTING GROUNDING
 ELECTRODES, THE GROUNDING ELECTRODE(S)
 REQUIRED IN PART III OF THIS ARTICLE
 SHALL BE INSTALLED.
  
 3} 210.8(A) DWELLING UNITS. ALL
 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE
 LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 (2) GARAGES, AND ALSO ACCESSORY
 BUILDINGS THAT HAVE A FLOOR LOCATED AT
 OR BELOW GRADE LEVEL NOT INTENDED AS
 HABITABLE ROOMS AND LIMITED TO STORAGE
 AREAS, WORK AREAS, AND AREAS OF SIMILAR
 USE.
  