| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} 225.31 DISCONNECTING MEANS. |
| | MEANS SHALL BE PROVIDED FOR |
| | DISCONNECTING ALL UNGROUNDED CONDUCTORS |
| | THAT SUPPLY OR PASS THROUGH THE BUILDING |
| | OR STRUCTURE. SHOW LOCATION ON PLAN. |
| | |
| | 2} 250.32 TWO OR MORE BUILDINGS OR |
| | STRUCTURES SUPPLIED FROM A COMMON |
| | SERVICE. |
| | (A) GROUNDING ELECTRODE. WHERE TWO OR |
| | MORE BUILDINGS OR STRUCTURES ARE |
| | SUPPLIED FROM A COMMON AC SERVICE BY A |
| | FEEDER(S) OR BRANCH CIRCUIT(S), THE |
| | GROUNDING ELECTRODE(S) REQUIRED IN PART |
| | III OF THIS ARTICLE AT EACH BUILDING OR |
| | STRUCTURE SHALL BE CONNECTED IN THE |
| | MANNER SPECIFIED IN 250.32(B) OR (C). |
| | WHERE THERE ARE NO EXISTING GROUNDING |
| | ELECTRODES, THE GROUNDING ELECTRODE(S) |
| | REQUIRED IN PART III OF THIS ARTICLE |
| | SHALL BE INSTALLED. |
| | |
| | 3} 210.8(A) DWELLING UNITS. ALL |
| | 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN THE |
| | LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL. |
| | |
| | (2) GARAGES, AND ALSO ACCESSORY |
| | BUILDINGS THAT HAVE A FLOOR LOCATED AT |
| | OR BELOW GRADE LEVEL NOT INTENDED AS |
| | HABITABLE ROOMS AND LIMITED TO STORAGE |
| | AREAS, WORK AREAS, AND AREAS OF SIMILAR |
| | USE. |
| | |