| 2006-04-28 00:00:00 | *** DENIED *** |
| | 1) MANUAL J CALCULATIONS ARE CALLING FOR |
| | A TOTAL OF 25,892 SENSIBLE BTU'S, |
| | MECHANICAL PLANS ARE CALLING FOR A TOTAL |
| | OF 47,800 SENSIBLE BTU'S, THE PLANS CAN |
| | ONLY CALL FOR 20% MORE THAN THE MANUAL J |
| | CAL'S PLEASE CORRECT, PER 2004 FBC CH. |
| | 13, 607.1.ABC.1.1 . |
| | |
| | 2) PLEASE CORRECT THE FLOOR SIZE FOR |
| | ZONE 1 IN THE MANUAL J CAL'S. |
| | |
| | 3) A 12" RETURN AIR DUCT TO AHU #3 |
| | APPEARS TO SMALL BOR A 3 TON A/C SYSTEM, |
| | PLEASE CORRECT. |
| | |
| | 4)PLEASE SHOW THE SIZE OF THE R/A RIDGE |
| | DUCT IN A/C CLOSET #3. |
| | |
| | 5)RETURN AIR TRANSFER DUCT TO FAMILY |
| | ROOM IS UNDER SIZED, SEE NOTE #7. |
| | |
| | 6) AS REQUESTED 3-14-06 #7, RETURN AIR |
| | TRANSFER DUCT TO MASTER BEDROOM IS UNDER |
| | SIZED, SEE NOTE #7 (C) EXCEPT.. |
| | |
| | 7)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |