| Plan Review Notes For Permit 06021135 |
| Permit Number |
06021135 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-27 00:00:00 | | | | | | | PLEASE SEE ARTICLE 225.31 AND 225.32 , | | | 2002, NEC. WHICH READ AS FOLLOWS. | | | | | | 225.31 DISCONNECTING MEANS. | | | MEANS SHALL BE PROVIDED FOR | | | DISCONNECTING ALL UNGROUNDED CONDUCTORS | | | THAT SUPPLY OR PASS THROUGH THE BUILDING | | | OR STRUCTURE. | | | 225.32 LOCATION. | | | THE DISCONNECTING MEANS SHALL BE | | | INSTALLED EITHER INSIDE OR OUTSIDE OF | | | THE BUILDING OR STRUCTURE SERVED OR | | | WHERE THE CONDUCTORS PASS THROUGH THE | | | BUILDING OR STRUCTURE. THE DISCONNECTING | | | MEANS SHALL BE AT A READILY ACCESSIBLE | | | LOCATION NEAREST THE POINT OF ENTRANCE | | | OF THE CONDUCTORS. FOR THE PURPOSES OF | | | THIS SECTION, THE REQUIREMENTS IN 230.6 | | | SHALL BE PERMITTED TO BE UTILIZED. | | | | | | ALSO SEE ARTICLE 250.32(A), TO DETERMINE | | | HOW TO INSTALL A GROUNDING ELECTRODE AT | | | THAT BUILDING, IN THIS CASE, THE MAIN | | | HOUSE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|