| 2006-03-14 00:00:00 | *** DENIED *** |
| | 1) ARCHITECT'S LICENSE NUMBER MUST |
| | APPEAR IN THE TITLE BLOCK, PER FAC |
| | 61G1-16.004 . |
| | |
| | 2) ENERGY CALCULATIONS NEED TO BE SIGNED |
| | BY OWNER/AGENT. |
| | |
| | 3) PLEASE SHOW TOTAL COOLING BTU'S. AND |
| | SENSIBLE COOLING BTU'S. ON MECHANICAL |
| | PLANS. |
| | |
| | 4) PLANS ARE SHOWING AN EXHUST FAN IN |
| | THE LAUNDRY ROOM WITH A GAS WATER |
| | HEATER, THIS WILL REMOVE THE COMBUSTION |
| | AIR FROM THE ROOM PLEASE CORRECT. |
| | |
| | 5) PLEASE SHOW THE SIZE OF THE RETURN |
| | AIR GRILL TO AHU #4. |
| | |
| | 6) RETURN AIR TRANSFER DUCTS TO THE DEN. |
| | AND PLAYROOM ARE UNDER SIZED, SEE NOTE |
| | #8 (A). |
| | |
| | 7) RETURN AIR TRANSFER DUCT TO THE |
| | MASTER SUITE IS TO SMALL, SEE NOTE #8 |
| | (A) AND (C) "EXCEPT". |
| | |
| | 8)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |