| 2006-06-16 00:00:00 | **UNSAT ** 2ND REVIEW** |
| | |
| | PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| | REVIEW AND SOME NEW COMMENTS DUE TO |
| | PLANS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | WITH PANEL SCHEDULE FOR MDP. PLEASE SEE |
| | T-1. |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE INDICATE ALL GROUNDING |
| | ATTACHMENTS FOR THE TRANSFORMERS ARE |
| | REQUIRED PER 250.30,250.66 ETC. |
| | PLEASE SEE T-1 DOES NOT INDICATE THIS |
| | ATTACHMENT.? |
| | |
| | 3) NOTE: PLEASE SEE 450.3 FOR MAX OCP |
| | FOR THE TRANSFORMERS AS SHOWN TO BE |
| | 125%. |
| | PLEASE SEE MDP 70A 60A FOR T-1 AND PP |
| | RISER SHOWS 60A FOR T-2. |
| | PLEASE SEE RISER FOR T-2, IS THIS A |
| | 3-POLE DISC WITH ONLY 2-PHASE'S BEING |
| | USED? |
| | THIS IS BEING ASSUMED AT THIS TIME, BUT |
| | PLEASE CLARIFY. |
| | PLEASE SEE DISC NOTE #3, 70A'S?? |
| | PLEASE CORRELATE AT STATED IN NOTE #1 |
| | ABOVE. |
| | |
| | 4) NOTE: PLEASE SEE THE CODES ON 1-E-1 |
| | SHALL BE REFLECTED TO THE 2004 FBC AND |
| | THE 2002 NEC. |
| | |
| | 5) NOTE: PLEASE SEE A NOTE OR |
| | INFORMATION COULD NOT BE LOCATED |
| | DENOTING ANY CLASS LOCATIONS. |
| | |
| | ** PLEASE SEE BUILDING REVIEW COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |