| 2006-03-29 00:00:00 | ************** UNSAT *************** |
| | |
| | 1) NOTE: PLEASE LIST CURRENT CODES IN |
| | EFFECT, NFPA-70 2002, NFPA-101 2003. |
| | |
| | 2) NOTE: PLEASE SEE SERVICE GROUNDING |
| | ELECTRODE SYSTEM. SHOWS BLDG STEEL, IS |
| | THIS NOT THE FOOTER STEEL OR IS THERE |
| | BOTH? IF BOTH THEN FOOTER STEEL WILL |
| | ALSO BE REQUIRED. IF NO "BLDG STEEL", |
| | PLEASE CALL OUT FOR FOOTER STEEL. |
| | 250.50 |
| | |
| | 3) NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | SYSTEM AT TRANSFORMER PER 250.30,250.66. |
| | PLEASE INCLUDE SIZE OF THE GEC. |
| | 215.5 |
| | |
| | 4) NOTE: PLEASE SEE MAX OCP FOR |
| | TRANSFORMER SHALL BE BASED ON 450.3 |
| | PLEASE KNOW, THE KVA FOR T-2 IS NOT |
| | CLEAR, A MODEL # IS SHOWN WHICH TENDS TO |
| | LEAD TO THIS TRANSFORMER AS ALSO BEING |
| | 25 KVA? IF SO, IN EITHER CASE PLEASE SEE |
| | 450.3 FOR MAX OCP. |
| | 125%). |
| | |
| | 5) NOTE: PLEASE SEE T-2, AND SEE 240.21, |
| | RISER SHOWS "TAPPING" A "TAP". PLEASE |
| | KNOW THIS NOT PERMITTED. A TAP SHALL |
| | TERMINTE IN A SINGLE MEANS OF OCP. |
| | 215.5 |
| | |
| | 6) NOTE: PLEASE SEE 250.6,250.24B. AN |
| | "EQUIPMENT GROUNDING CONDUCTOR" IS BEING |
| | SHOWN FROM METER TO THE FIRST MEANS OF |
| | DISCONNECT FOR MDP SERVICE. |
| | PLEASE KNOW, THIS SHALL ONLY BE |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE SEE CONDUCTORS AND |
| | CONDUIT SHOWN ON MDP RISER FOR FEED TO |
| | T-1?? |
| | SEEMS TO BE AN ERROR/ OR MISPRINT. |
| | 215.5 |
| | |
| | 8) NOTE: PLEASE SPECIFY ANY AREAS PER |
| | NEC ART 500. |
| | PLEASE LIST ANY AREA CHEMICAL FOR FUEL, |
| | MIXING ETC WHICH MAY CREATE AN CLASS |
| | LOCATION. PLEASE LIST OR SHOW. |
| | |
| | 9) NOTE: PLEASE SPECIFY DEPT OF CONDUITS |
| | PER 300.5 IN AREAS ON SITE PLANS E-1 |
| | |
| | PLEASE SEE NAY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |