| Plan Review Notes For Permit 06021123 |
| Permit Number |
06021123 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-29 00:00:00 | DENIED; | | | 1.PLANS ARE TO BE REVIEWED AND APPROVED | | | BY THE DIVISION OF HOTEL AND RESTAURANTS | | | BEFORE RESUB TO THE CITY. | | | 2.A SERVICE SINK IS REQUIRED PER | | | FBC-2004 PLUMBING TABLE 403.1. | | | 3.FLOOR SINKS ARE REQUIRED FOR INDIRECT | | | WASTES. (SODA DISPENSOR, ICE MACHINE, | | | AND STEAM TABLE). | | | 4.FOOD PREP AREA DOES NOT HAVE A SINK | | | FOR STORING OR PREPARATION OF FOOD. SO | | | THE 3 COMPARTMENT SINK SHOULD DRAIN | | | INDIRECTLY SEC. 802.1.1. | | | 5.WATER HEATER. SHOW DETAIL OF PLATFORM, | | | AND LIST MATERIAL TO BE USED. SHOW PAN | | | DRAIN AND LOCATION OF DISPOSAL AREA FOR | | | PAN DRAIN. COMPLY WITH SEC.504.7.2. | | | THERMAL EXPANSION CONTROL IS ALSO | | | REQUIRED PER. SEC. 607.3 | | | 6.PLEASE CHECK WITH RODMEY COMPO | | | (ENVIRONMENT COMPLIANCE TECHNICIAN) WITH | | | THE UTILITY DEPARTMENT FOR A GREASE TRAP | | | WAVER. 822-2200 EXT 2272 | | | E-MAIL, [email protected]. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|