Plan Review Notes
Plan Review Notes For Permit 06021083
Permit Number 06021083
Review Stop E
Sequence Number 3
Notes
Date Text
2006-08-06 00:00:00**** UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE SOME COMMENTS FROM THE TWO
  
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
 NOTES BELOW ARE TAKEN FROM 2ND REVIEW.
  
  
 1) NOTE: NO, PLEASE SEE OVER RIDE
 DEVICES ARE NOT SHOWN AND THE DETAILS OF
 THE TYPE AND HRS OF OVERRIDE IS NOT ON
 PLANS. RESPONSE LTR MENTIONS THIS IS
 DONE, HOWEVER PLEASE SEE THESE
 OVERIRIDES COULD NOT BE LOCATED AT THE
 POINT OF ENTRANCE TO THE SPACE. PLEASE
 SEE FRONT AND REAR INGRESS/EGRESS.
 PLEASE SEE SEPARATE SPACES AS ALSO
 PREVIOUSLY REQUESTED. PLEASE SEE ANY
 AREAS W/ FLR TO CEILING HEIGHT
 PARTITIONS. (BATH RMS ETC)
 CALCS SEEM TO BE OK, AND OTHER ITEMS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NOTE #2 FROM
 PREVIOUS REVIEW WHICH WAS TYPED IN
 ERROR. PLEASE SEE A 413 WAS TYPED
 INSTEAD OF 415. IN EITHER CASE THE NOTES
 REFERENCED WAS TO PROVIDE LIGHTING
 CONTROLS , SCHEDULING OVER -RIDES ETC.
 PLEASE SEE THAT RESPONSE WAS FOR VOLTAGE
 DROP WHICH WAS ALSO CORRECT.
 PLEASE SEE ALL OF FBC 2004 CHAPTER 13 AS
 ALKL OF THE ABOVE APPLIES.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3
 PLEASE SEE THAT ENERGY CALCULATIONS MUST
 BE DONE PER EITHER SPACE BY SPACE OR
 ENTIRE AREA.
 PLEASE ALSO SEE FORM WHICH IS TO BE
 USED.
 13-415.1.AB.1, 13-415.1.ABC.1
  
 2) NOTE: NO, PLEASE SEE TWO PREVIOUS
 REVIEW WHICH STATED THE ADDTIONAL
 SERVICE IS NOT AND SHALL NOT BE GRANTED
 UNLESS PROVIDING COMPELETED INFORMATION
 FOR "SPECIAL PERMISSION" WHICH MUST BE
 GRANTED BY THE AHJ. PLEASE SEE 230.2.
 DUE TO INSUFFICIENT INFORMATION AND
 BASED ON WHAT HAS BEEN SUBMITTED THE
 ADDITIONAL SERVICE IS NOT GRANTED.
 PLEASE SEE THIS IS ONE BUILDING AND THIS
 IS A TENANT SPACE IN ONE BUILDING. IN
 ORDER FOR THIS SPACE TO BE CONSIDERED A
 SEPARATE "BUILDING" ON ITS OWN FOR A
 SEPARATE SERVICE, IT MUST CONTAIN "FIRE
 WALLS ON EACH SIDE. PLEASE SEE FBC 2004
 DEFINITIONS OF FIREWALL, WHICH IS 4HRS
 AND IS CONSTRUCTED AS TO ALLOW COLLAPSE
 ON EACH SIDE WITHOUT AFFECTING THE
 STRUCTURAL INTEGRITY OF ADJACENT
 BUILDING. PLEASE KNOW AS THIS LOCATION
 DOES NOT CONTAIN SUCH STRUCTURAL
 ELEMENTS, THEN ONLY THE EXCEPTIONS
 ALLOWED IN THE NEC WILL BE CONSIDERED.
 AT THIS TIME ANDBASED ON PLANS NO
 CONSIDERATION CAN BE MADE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS STILL DO NOT
 INDICATE LOCATION OF THE EXISTING
 SERVICE, LOADS ETC.
 PLEASE SEE A NOTE ON THE RISER DIAGRAM
 MENTIONS SERVICE IS EXISTING, YET
 SERVICE IS ALSO NOTED AS NEW??
 PLEASE PREVIOUS NOTES WITH RESPECT TO
 THE SERVICE AND LOCATIONS.
 THE NEW SERVICE AS SHOWN IS NOT APPROVED
 BY THIS AHJ AT THIS TIME.
 IF THIS IS BEING FED FROM AN EXISTING
 LOCATION OR GUTTER OR OTHER MAIN, PLEASE
 SHOW.
 230.2, 230.72, 230.70, 215.5
  
 3) NOTE:OK,PLEASE BE SURE TO DO THE
 SAME WHEN RESUBMITTING PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PREVIOUS REVIEW
 NOTES WHERE IT WAS REQUESTED THAT ALL
 THE OLD/VOIDED SHEETS BE COMPLETELY
 REMOVED FROM SETS AND ONLY TO INSERT NEW
 REVISED SHEETS INTO SETS FOR REVIEW AND
 STAMPING. PLEASE SEE THIS WAS NOT DONE.
 PLEASE DO SO AND ONLY SUBMIT ONE COPY OF
 THE OLD/VOIDED REMOVED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717