| Date |
Text |
| 2006-08-06 00:00:00 | **** UNSAT 3RD REVIEW ****** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM THE TWO |
| | |
| | PREVIOUS REVIEW STILL NEED TO BE |
| | ADDRESSED. |
| | NOTES BELOW ARE TAKEN FROM 2ND REVIEW. |
| | |
| | |
| | 1) NOTE: NO, PLEASE SEE OVER RIDE |
| | DEVICES ARE NOT SHOWN AND THE DETAILS OF |
| | THE TYPE AND HRS OF OVERRIDE IS NOT ON |
| | PLANS. RESPONSE LTR MENTIONS THIS IS |
| | DONE, HOWEVER PLEASE SEE THESE |
| | OVERIRIDES COULD NOT BE LOCATED AT THE |
| | POINT OF ENTRANCE TO THE SPACE. PLEASE |
| | SEE FRONT AND REAR INGRESS/EGRESS. |
| | PLEASE SEE SEPARATE SPACES AS ALSO |
| | PREVIOUSLY REQUESTED. PLEASE SEE ANY |
| | AREAS W/ FLR TO CEILING HEIGHT |
| | PARTITIONS. (BATH RMS ETC) |
| | CALCS SEEM TO BE OK, AND OTHER ITEMS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NOTE #2 FROM |
| | PREVIOUS REVIEW WHICH WAS TYPED IN |
| | ERROR. PLEASE SEE A 413 WAS TYPED |
| | INSTEAD OF 415. IN EITHER CASE THE NOTES |
| | REFERENCED WAS TO PROVIDE LIGHTING |
| | CONTROLS , SCHEDULING OVER -RIDES ETC. |
| | PLEASE SEE THAT RESPONSE WAS FOR VOLTAGE |
| | DROP WHICH WAS ALSO CORRECT. |
| | PLEASE SEE ALL OF FBC 2004 CHAPTER 13 AS |
| | ALKL OF THE ABOVE APPLIES. |
| | PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3 |
| | PLEASE SEE THAT ENERGY CALCULATIONS MUST |
| | BE DONE PER EITHER SPACE BY SPACE OR |
| | ENTIRE AREA. |
| | PLEASE ALSO SEE FORM WHICH IS TO BE |
| | USED. |
| | 13-415.1.AB.1, 13-415.1.ABC.1 |
| | |
| | 2) NOTE: NO, PLEASE SEE TWO PREVIOUS |
| | REVIEW WHICH STATED THE ADDTIONAL |
| | SERVICE IS NOT AND SHALL NOT BE GRANTED |
| | UNLESS PROVIDING COMPELETED INFORMATION |
| | FOR "SPECIAL PERMISSION" WHICH MUST BE |
| | GRANTED BY THE AHJ. PLEASE SEE 230.2. |
| | DUE TO INSUFFICIENT INFORMATION AND |
| | BASED ON WHAT HAS BEEN SUBMITTED THE |
| | ADDITIONAL SERVICE IS NOT GRANTED. |
| | PLEASE SEE THIS IS ONE BUILDING AND THIS |
| | IS A TENANT SPACE IN ONE BUILDING. IN |
| | ORDER FOR THIS SPACE TO BE CONSIDERED A |
| | SEPARATE "BUILDING" ON ITS OWN FOR A |
| | SEPARATE SERVICE, IT MUST CONTAIN "FIRE |
| | WALLS ON EACH SIDE. PLEASE SEE FBC 2004 |
| | DEFINITIONS OF FIREWALL, WHICH IS 4HRS |
| | AND IS CONSTRUCTED AS TO ALLOW COLLAPSE |
| | ON EACH SIDE WITHOUT AFFECTING THE |
| | STRUCTURAL INTEGRITY OF ADJACENT |
| | BUILDING. PLEASE KNOW AS THIS LOCATION |
| | DOES NOT CONTAIN SUCH STRUCTURAL |
| | ELEMENTS, THEN ONLY THE EXCEPTIONS |
| | ALLOWED IN THE NEC WILL BE CONSIDERED. |
| | AT THIS TIME ANDBASED ON PLANS NO |
| | CONSIDERATION CAN BE MADE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS STILL DO NOT |
| | INDICATE LOCATION OF THE EXISTING |
| | SERVICE, LOADS ETC. |
| | PLEASE SEE A NOTE ON THE RISER DIAGRAM |
| | MENTIONS SERVICE IS EXISTING, YET |
| | SERVICE IS ALSO NOTED AS NEW?? |
| | PLEASE PREVIOUS NOTES WITH RESPECT TO |
| | THE SERVICE AND LOCATIONS. |
| | THE NEW SERVICE AS SHOWN IS NOT APPROVED |
| | BY THIS AHJ AT THIS TIME. |
| | IF THIS IS BEING FED FROM AN EXISTING |
| | LOCATION OR GUTTER OR OTHER MAIN, PLEASE |
| | SHOW. |
| | 230.2, 230.72, 230.70, 215.5 |
| | |
| | 3) NOTE:OK,PLEASE BE SURE TO DO THE |
| | SAME WHEN RESUBMITTING PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PREVIOUS REVIEW |
| | NOTES WHERE IT WAS REQUESTED THAT ALL |
| | THE OLD/VOIDED SHEETS BE COMPLETELY |
| | REMOVED FROM SETS AND ONLY TO INSERT NEW |
| | REVISED SHEETS INTO SETS FOR REVIEW AND |
| | STAMPING. PLEASE SEE THIS WAS NOT DONE. |
| | PLEASE DO SO AND ONLY SUBMIT ONE COPY OF |
| | THE OLD/VOIDED REMOVED SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |