Plan Review Notes
Plan Review Notes For Permit 06021083
Permit Number 06021083
Review Stop G
Sequence Number 2
Notes
Date Text
2006-07-03 00:00:00PAUL SCHMITZ
 FBC 2004 FUEL GAS CODE, PLAN REVIEW
  
 UNSAT
  
 PREVIOUS NOTE.
  
 10)EMERGENCY HOOD SHUT OFF VALVE
 (E) AUTOMATIC SHUT OFF VALVE.
  
 GAS EMERGENCY SOV TO BEINSTALLED BELOW
 THE CEILIMG. MANUAL SOV AND UNION
 UPSTREAM OF EMERGENCY SHUT OFF VALVE.
  
 PLACED CALL TO ENG. OF RECORD
 MR.GARY STENLUND 813-251-6848
 TO CHANGE TO BELOW CEILING. 7-3-06
  
 END OF COMMENTS QUESTIOINS561-805-6692