| Date |
Text |
| 2006-06-20 00:00:00 | *********UNSAT ********* |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW. |
| | |
| | |
| | 1) NOTE: PELASE SEE NOTE #2 FROM |
| | PREVIOUS REVIEW WHICH WAS TYPED IN |
| | ERROR. PLEASE SEE A 413 WAS TYPED |
| | INSTEAD OF 415. IN EITHER CASE THE NOTES |
| | REFERENCED WAS TO PROVIDE LIGHTING |
| | CONTROLS , SCHEDULING OVER -RIDES ETC. |
| | PLEASE SEE THAT RESPONSE WAS FOR VOLTAGE |
| | DROP WHICH WAS ALSO CORRECT. |
| | PLEASE SEE ALL OF FBC 2004 CHAPTER 13 AS |
| | ALKL OF THE ABOVE APPLIES. |
| | PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3 |
| | PLEASE SEE THAT ENERGY CALCULATIONS MUST |
| | BE DONE PER EITHER SPACE BY SPACE OR |
| | ENTIRE AREA. |
| | PLEASE ALSO SEE FORM WHICH IS TO BE |
| | USED. |
| | 13-415.1.AB.1, 13-415.1.ABC.1 |
| | |
| | 2) NOTE: PLEASE SEE PLANS STILL DO NOT |
| | INDICATE LOCATION OF THE EXISTING |
| | SERVICE, LOADS ETC. |
| | PLEASE SEE A NOTE ON THE RISER DIAGRAM |
| | MENTIONS SERVICE IS EXISTING, YET |
| | SERVICE IS ALSO NOTED AS NEW?? |
| | PLEASE PREVIOUS NOTES WITH RESPECT TO |
| | THE SERVICE AND LOCATIONS. |
| | THE NEW SERVICE AS SHOWN IS NOT APPROVED |
| | BY THIS AHJ AT THIS TIME. |
| | IF THIS IS BEING FED FROM AN EXISTING |
| | LOCATION OR GUTTER OR OTHER MAIN, PLEASE |
| | SHOW. |
| | 230.2, 230.72, 230.70, 215.5 |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW |
| | NOTES WHERE IT WAS REQUESTED THAT ALL |
| | THE OLD/VOIDED SHEETS BE COMPLETELY |
| | REMOVED FROM SETS AND ONLY TO INSERT NEW |
| | REVISED SHEETS INTO SETS FOR REVIEW AND |
| | STAMPING. PLEASE SEE THIS WAS NOT DONE. |
| | PLEASE DO SO AND ONLY SUBMIT ONE COPY OF |
| | THE OLD/VOIDED REMOVED SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |