| Plan Review Notes For Permit 06021083 |
| Permit Number |
06021083 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-20 00:00:00 | ******DENIED****** | | | | | | 1) IT WOULD APPEAR THAT THE OCCUPANT | | | LOAD BASED ON 15 SQ' PER PERSON IS BASED | | | ON ASSEMBLY OCCUPANCY, HOWEVER THE | | | OCCUPANT LOAD < 50 DOES NOT MEET THE | | | DEFINITION CRITERIA OF NFPA 101, 2003 | | | EDITION SECTION 3.3.152.2. | | | | | | 2) CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | 3) IN ADDITION TO HOOD/SUPPRESSION | | | EQUIPMENT, SEPARATE SHOP DRAWING AND | | | PERMITS ARE REQUIRED FOR FIRE SPRINKLER | | | AND FIRE ALARM REMODEL. | | | | | | 4) DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 5) 2A-10B,C RATED FIRE EXTINGUISHER(S) | | | ARE REQUIRED AT DISTANCES NOT TO EXCEED | | | 75' TRAVEL DISTANCE. "K" TYPE FIRE | | | EXTINGUISHER REQUIRED IN KITCHEN. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|