| 2006-03-29 00:00:00 | ***** UNSAT ******** |
| | |
| | |
| | 1)NOTE: PLEASE REFERENCE THE FOLLOWING |
| | CODES. NFPA-70 2002, NFPA-101 2003, |
| | NFPA-72 2002. |
| | |
| | 2)NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-413.1.ABC.1.1, & .2. |
| | PLEASE PROVIDE SCHEDULING, CIRCUITING |
| | AND SPACE CONTROL DEVICES FOR OVERIDES |
| | AND SPACE CONTROL OVERIDE FOR SPACE. |
| | |
| | 3)NOTE: PLEASE SEE SERVICE AS SHOWN DOES |
| | NOT DEPICT EXISTING SERVICE AND |
| | LOCATION. PLEASE KNOW, AN ADDITTIONAL |
| | SERVICE MAY NOT BE GRANTED. PLEASE |
| | PROVIDE COMPLETE LAYOUT AND LOCATIONS OF |
| | EXISTING SERVICE, SIZE, LOAD |
| | CALCULATIONS, ETC |
| | THESE ITEMS WILL BE REVIEWED TO SEE "IF" |
| | AN ADDITIONAL SERVICE MAY BE GRANTED. |
| | PLEASE KNOW, SERVICE AS SHOWN IS NOT |
| | PERMITTED AT THIS TIME. |
| | 230.2,230.70.230.72, 215.5 |
| | |
| | 4)NOTE: PLEASE VERIFY SERVICE AS SHOWN, |
| | AS THE FPL METERING DEVICE IS SHOWN ON |
| | THE LOAD SIDE OF THE MAIN DISCONNECT. |
| | PLEASE SEE FPL MININUM SERVICE |
| | GUIDELINES. |
| | THE DISCONNECT IS NOT PERMITTED AS |
| | SHOWN. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | CONDUCTOR DOES NOT SHOW ANY GROUNDING |
| | ELECTRODE SYSTEM, ONLY A BOND TO |
| | EXISTINGMAIN NEUTRAL. THIS IS UNCLEAR |
| | AT THIS TIME. |
| | IF MORE THAN ONE SERVICE IS PERMITTED, |
| | THE TWO OR MORE GROUNDING ELECTRODE |
| | SYSTEMS SHALL BE BONDED TOGETHER, |
| | HOWEVER THERE STILL MUST BE A GROUNDING |
| | ELECTRODE SYSTEM. |
| | 250.50,250.92 ETC |
| | |
| | 6) NOTE: PLEASE SEE COLOR CODING AS |
| | SHOWN FOR 277/480V SYSTEMS SHALL BE BE |
| | BROWN/PURPLE/YELLOW, AS "ORANGE" IS |
| | STRICLY FOR A DELTA "HIGH-LEG SYSTEM |
| | WHICH DOES NOT APPEAR TO BE SHOWN. |
| | |
| | 7) NOTE: PLEASE SUBMIT ALL AIC RATINGS |
| | FOR ALL NEW MAINS/ SERVICE EQUIPMENT. |
| | 110.9,215.5 |
| | |
| | 8)NOTE: PLEASE KNOW, ANY "LOCK-OUT" |
| | DEVICS MUST BE APPROVED BY THE AHJ, |
| | BEFORE INSTALLATION. PLEASE KNOW, THERE |
| | ARE MANY DEVICES WHICH ARE NOT |
| | ACCEPTABLE TO THIS AHJ AS THE |
| | DISCONNECTING LOCK OUT DEVICE. |
| | THE ONLY LOCK OUT DEVICE ACCEPTABLE, |
| | MUST BE AN INTEGRAL PART OF THE BREAKER. |
| | IT SHALL NOT HAVE THE ABILITY TO BE |
| | REMOVED UNLESS BREAKER IS REMOVED FROM |
| | PANEL. |
| | 90.4,422.31 |
| | |
| | 9) NOTE: PLEASE SEE THAT PANEL SCHEDULE |
| | SHALL REFLECT THE EQUIPMENT INSTEAD OF A |
| | NUMERICAL SCHEDULE TO REFELCT AN |
| | EQUIPMENT SCHEDULE WHICH MAY/MAY NOT BE |
| | LOCATED IN PANEL. |
| | PLEASE ADJUST PANEL SCHEDULE TO |
| | CORRELATE WITH EQUIPMENT SCHEDULE A THIS |
| | TIME.408.4, 215.5 |
| | |
| | 10) NOTE: PLEASE CLARIFY CIRCUTING FOR |
| | RT GFI'S. PLANS INDICATE #24? |
| | PLEASE CORRELATE WITH CIRCUIT INTENDED |
| | FOR USE. |
| | 215.5 |
| | |
| | 11)NOTE: PLEASE SEE CODE REFLECTED ON |
| | PLANS FOR KTICHENGFI/GFI RECEPTS |
| | PROTECTIONSEEMS TO BE MISPRINTED. |
| | PLEASE SEE 2002 NEC , WHICH INDICATE |
| | 210.8B3". "B2" IS FOR ROOF TOP RECEPTS. |
| | |
| | 12) NOTE: PLEASE SEE 220.12A FOR LOAD ON |
| | "SHOW WINDOWS". PLEASE SPECIFY THE |
| | LINEAR FT.IT APPEARS THE OPTION SHOWN IN |
| | 220.3(B)(7) IS BEING USED IN LIEU OF |
| | FT/VA. |
| | PLEASE ONLY VERIFY. |
| | |
| | ** PLEASE BE SURE TO SEE COMMENTS FROM |
| | OTHER REVIEWERS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO COMPLETELT REMOVE |
| | ALL OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONLY ONE SET OF ANY OLD/VOIDED REMOVED |
| | SHEETS NEED BE SUBMITTED BACK SEPARTELY |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMITTHE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |