| Plan Review Notes For Permit 06021054 |
| Permit Number |
06021054 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-14 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE ON | | | FORM 600A-04 (2004) PER FBC 13-600.3.A . | | | | | | 2) ENERGY CAL'S. NEED TO BE SIGNED BY | | | OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2 | | | | | | 3) PLEASE SEE MANUAL J CAL'S. LAST PAGE | | | TOTAL SENSIBLE GAIN 14847, THE EQUIPMENT | | | BEING INSTALLED SENSIBLE BTU'S. CAN NOT | | | BE MORE THAN 20% OVER THE MANUAL J | | | CAL'S. PER 2004 FBC 13-607.1.ABC.1.1, | | | PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|