| Plan Review Notes For Permit 06021051 |
| Permit Number |
06021051 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-30 00:00:00 | | | | | | | ******PROVISO******* | | | | | | EMERGENCY EGRESS PER R310 FBC: | | | MIN. NET CLEAR OPENING OF 5 SQ.FT. ON | | | GRADE FLOOR. MIN. NET CLEAR OPENING ALL | | | OTHER FLOORS OF 5.7 SQ.FT. IN BOTH CASES | | | THE MIN.NET CLEAR HEIGHT SHALL BE 24" | | | AND THE NET CLEAR WIDTH SHALL BE 20" | | | | | | REPLACEMENT WINDOWS THAT MEET OR ARE | | | GREATER THAN THESE REQUIREMENTS SHALL BE | | | ALLOWED A MAX. 5% REDUCTION IN CLEAR | | | OPENING DIMENSIONS PER 505 EXISTING FBC | | | | | | REPLACEMENT OF WINDOWS NEED NOT MEET | | | THESE REQUIREMENTS IF THERE IS NO | | | REDUCTION IN THE NET CLEAR OPENING SIZE | | | BETWEEN THE EXISTING AND NEW WINDOWS |
|