| Date |
Text |
| 2006-12-12 09:21:22 | PASS PRIVISO | | | ACCORDING TO INSTALLATION INSTRUCTIONS THE ROOF TOP | | | PACKAGE UNIT WILL PROVIDE UP TO 2,400 CFM. THE DESIGN | | | CAPACITY OF THE UNIT IS GREATER THAN 2000 CFM, SO FAN | | | SHUTDOWN IS REQUIRED. SECTION 606.2.1 2001 FBC (M) . | | | ADDITIONAL PLANS AND PERMITS REQUIRED FOR HOOD,COOLERS | | | AND SUPPRESSION. | | | PLEASE REFER TO SECTION 606.4.1 SUPERVISION. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | 2006-11-28 20:06:31 | NEW SHEETS/INFORMATION |
|