| 2006-10-01 00:00:00 | *** UNSAT 3RD REVIEW *** |
| | |
| | ** PLEASE KNOW, PLANS ARE STILL ONLY |
| | BEING SUBMITTED FOR "'PLAN REVIEW** AND |
| | HAVE NOT BEEN SUBMITTED FOR PERMIT TO |
| | DATE. |
| | |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW STILL APPLY. MOST WERE |
| | ADDRESSED. |
| | PLEASE KNOW, FS 553.80(2)(B) DOES NOT |
| | APPLY AS PLANS HAVE NOT BEEN SUBMITTED |
| | FOR PERMIT. |
| | |
| | |
| | *** NOTES FOR ELECTRICAL ENGINEERING |
| | FIRM WERE ADDRESSED AND ARE OK. |
| | |
| | 1) PLEASE SEE NEW NOTE #12 BELOW FROM |
| | PREVIOUS REVIEW AS THE TITLE BLOCKS DO |
| | NOT CONTAIN THE LICENSING INFORMATION |
| | FOR THE ARCHITECT/ DESIGNER "TURNKEY |
| | CONCEPTS" |
| | PLEASE SEE FS 481.203, 481.223(1)(A), |
| | AND 481.229 (1)(C). |
| | PLEASE IF THIS IS INDEED A "DESIGN" |
| | FIRM/OR "DRAFTING" FIRM, PLEASE KNOW IT |
| | HAS BEEN CONFIRMED WITH THE STATE'S |
| | LEGAL COUNSEL TO THE BOARD THAT THIS IS |
| | PROHIBITED. |
| | PLEASE KNOW, IF "TURNKEY" IS A LICENSED |
| | ARCHITECTURAL FIRM OFFERING |
| | ARCHITECTURAL SERVICES PLEASE INCLUDE |
| | ALL INFORMATION ON TITLE BLOCKS AS |
| | PREVIOUSLY REQUESTED. PLEASE KNOW A |
| | SERCH ON THE STATE'S WEBSITE HAS NOT |
| | COME UP WITH ANY INFORMATION ON SUCH |
| | COMPANY FROM THE DEPARTMENT OF BUSINESS |
| | AND PROFESSIONAL REGUALTION. |
| | ONE COPY OF ALL SAID PLANS WILL BE |
| | RETAINED AT THE REQUEST OF STATE'S |
| | PROSECUTING ATTORNEY. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE 2ND REVIEW ** |
| | ************* NEW NOTE ************ |
| | |
| | |
| | 12) NOTE: PLEASE SEE MISSING REQUIRED ON |
| | TITLE BLOCKS FOR ARCHITECT AND FIRM AS |
| | SHOWN. |
| | PLEASE SEE FAC 61G1-16.004, AND FS |
| | 481.219. |
| | MISSING PRINTED NAME AND LICENSE #. |
| | MISSING THE FIRM LICENSE #, ALSO KNOWN |
| | AS THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER. |
| | PLEASE KNOW, THIS IS REQUIRED ON ALL |
| | SHEETS WHICH CONTAIN THIS TITLE BLOCK |
| | AND WHICH ARE SIGNED, DATED AND SEALED |
| | BY THE ARCHITECT. |
| | PLEASE KNOW, THIS IS REQUIRED FOR ALL |
| | TRADES WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEWER(S). |
| | ** PLEASE SEE ARCHITECT HAS NOT DATED |
| | PLANS AS REQUIRED PER FS 481.221 |
| | |
| | ** PLEASE BE AWARE OF ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONLY ONE SET OF ANY OLD/VOIDED REMOVED |
| | SHEETS NEED BE SUBMITTED BACK SEPARTELY |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMITTHE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |