| 2006-10-05 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS LISTS: |
| | |
| | 1.)A NOTICE OF COMMENCEMENT REQUIRED, |
| | FS713.13. |
| | |
| | 2.)DECLARE OCCUPANCY, FBC 3. |
| | |
| | 6.)THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER FOR THE ARCHITECT FIRM IS TO BE |
| | ON EACH SHEET, FAC61G1-16.003, 004.SEE |
| | ALSO ELECTRIC REVIEWER?S COMMENTS |
| | REGARDING TURNKEY CONCEPTS, INC. |
| | |
| | 11.)PLANS STATE THAT THIS IS TYPE IV |
| | UPROTECTED.THIS IS HEAVY TIMBER.TO |
| | MY KNOWLEDGE, THERE IS ONLY ONE HEAVY |
| | TIMBER BUILDING IN THE CITY OF WEST PALM |
| | BEACH AND IT IS NOT THIS BUILDING. |
| | PLEASE CONFIRM THAT THIS IS A HEAVY |
| | TIMBER BUILDING. |
| | |
| | PLANS STATE THAT THIS BUILDING IS NOT |
| | REQUIRED TO BE SPRINKLED.YOU HAVE ALSO |
| | STATED THAT THE BUILDING IS 21450 SF. |
| | IT APPEARS THAT DUE TO THE SIZE OF THE |
| | BUILDING, IT IS LIKELY THAT IT IS |
| | REQUIRED BY CODE TO BE FULLY SPRINKLED. |
| | OUR RECORDS SHOW A FIRE ALARM/FIRE |
| | SPRINKLER PERMIT ISSUED IN THE PAST. |
| | ADDRESS. |
| | |
| | IF THE BUILDING IS REQUIRED TO BE |
| | SPRINKLED, FIRE SPRINKLER PLANS |
| | REQUIRED. |
| | |
| | 13.)SHOW ACCESS AISLES, FBC11-5.3. |
| | |
| | 15.)SHOW MANEUVERING CLEARANCE, DOOR |
| | 5, FBC 11 FIGURE 25, FBC11-4.13.6.THE |
| | DIMENSIONS SHOWN ARE FOR THE PUSH SIDE, |
| | THIS IS THE PULL SIDE OF THE DOOR. |
| | |
| | 16.)DOORS 5 AND 6, SHOW COMPLIANCE |
| | WITH FBC1008.1.8.8, LEAVE UNOBSTRUCTED |
| | HALF THE REQUIRED WIDTH.ALSO DOOR 4. |
| | THE RESPONSE LETTER STATES THAT THE REAR |
| | DOOR IS NOT AN EXIT.SEE ITEM 19. |
| | ALSO, EVEN IF ONE EXIT REQUIRED, SOMEONE |
| | WHO IS IN THE RESTROOM WILL EXIT THROUGH |
| | THE HALLWAY, WITH DOORS 4 AND 6 BLOCKING |
| | THE REQUIRED WIDTH.SOMEONE IN THE |
| | COOLER AREA ATTEMPTING TO EXIT THE |
| | KITCHEN AREA THROUGH DOOR 6 WOULD PASS |
| | DOOR 5, WHICH BLOCKS OVER HALF THE |
| | REQUIRED WIDTH. |
| | |
| | 19.)PLANS STATE THAT ONE EXIT IS |
| | REQUIRED.OCCUPANT LOAD DOES NOT MEET |
| | THE EXCEPTION FOR ONE EXIT FBC TABLE |
| | 1018.2.BASED ON INFORMATION PROVIDED, |
| | TWO EXITS ARE REQUIRED. |
| | |
| | NEW COMMENT: |
| | |
| | 20.)ENERGY CALCS STATE 1800 SF, PLANS |
| | STATE 1747.REVISE. |
| | |
| | 21.)WHAT IS THE CURRENT OCCUPANCY |
| | CLASSIFICATION OF THIS SPACE?I WAS |
| | UNABLE TO LOCATE AN OCCUPATIONAL LICENSE |
| | FOR THIS ADDRESS. |
| | |