Plan Review Notes
Plan Review Notes For Permit 06021049
Permit Number 06021049
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-07-10 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. EXITS SHALL REMAIN CLEAR AND
 ACCESSIBLE.
  
 4. ONLY 14" REMAIN FOR EXIT ACCESS IN
 THE REAR HALLWAY WHEN THE RESTROOM DOORS
 ARE IN THE OPEN POSITION. THE RESTROOM
 DOORS ARE 36" WIDE THAT OPEN ONTO A
 CORRIDOR THAT IS 50" WIDE. PLEASE
 REVISE.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY REQUIRED HOOD, DUCT, AND
 SUPPRESSION SYSTEMS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709