| Date |
Text |
| 2006-06-30 00:00:00 | *** UNSAT *** |
| | |
| | ** PLEASE KNOW, PLANS ARE STILL ONLY |
| | BEING SUBMITTED FOR "'PLAN REVIEW** AND |
| | HAVE NOT BEEN SUBMITTED FOR PERMIT TO |
| | DATE. |
| | |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW STILL APPLY. MOST WERE |
| | ADDRESSED. |
| | PLEASE KNOW, FS 553.80(2)(B) DOES NOT |
| | APPLY AS PLANS HAVE NOT BEEN SUBMITTED |
| | FOR PERMIT. |
| | |
| | |
| | |
| | 1)NOTE:NO, PLEASE SEE PLANS/COVER |
| | SHEETS REFLECTS THE 2004 FBC FOR THE |
| | ELECTRICAL CODE. PLEASE REFERENCE THE |
| | 2002 NFPA-70. |
| | PLEASE ALSO SEE ENERGY CALCULATIONS ARE |
| | STILL DESIGNED AND STATED PER 2001 FBC. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE PLANS REFERENCE THE |
| | 2001 FBC AND OTHER CODES NO LONGER IN |
| | AFFECT. PLEASE KNOW, THE NEW 2004 FBC |
| | WAS ADOPTED ON OCT, 1ST, 2005. |
| | PLEASE ALSO SEE OTHER CODES NOTES WHICH |
| | ARE NO LONGER IN AFFECT. PLEASE |
| | REFERENCE THE FOLLOWING |
| | CODES. NFPA-70 2002, NFPA-101 2003, |
| | NFPA-72 2002. |
| | |
| | |
| | 2)NOTE:NO, PLEASE SEE THIS NOTE WAS |
| | TYPED WITH THE "413" INSTEAD OF THE |
| | "415". THIS WAS IN ERROROF THIS |
| | OFFICE. THE NOTE WAS SHOWN ON PLANS FOR |
| | THE RESPONSE FROM THE DESIGNER INSTEAD |
| | OF OF PLACING ANY COMMENTS OR QUESTIONS |
| | IN A RESPONSE LETTER? |
| | PLEASE SEE THIS REQUIREMENT OF HAVING |
| | THE LIGHTING CONTROLS DOES APPLY AS |
| | STATED, IT IS IN A BUILDING LARGER THAN |
| | 5K SQ FT. PLEASE SEE THAT THIS SPACE IS |
| | A SEPARATELY METERED SPACE ON THIS SAME |
| | ELECTRICAL SERVICE. |
| | PLEASE SEE THAT THE TC PROVIDED IS OK, |
| | HOWEVER AN OVER RIDE DEVICE IS REQUIRED |
| | AT THE ENTRANCE(S) TO SPACE WHERE THE |
| | OCCUPANT CAN READLITY SEE THE LIGHTING |
| | BEING CONTROLLED. THIS OVERRIDE(S) |
| | DEVICE IF TIMER CANE ONLY HAVE A SETTING |
| | OF 4HRS. PLEASE SEE ANY SEPARATE SPACES |
| | WITH FLR TO CEILING HEIGHT PARTITIONS |
| | SHALL ALSO CONTAIN AN DEVICE OF SOME |
| | SORT EITHER MOTION SENSOR, INFARED, |
| | OCCUPANCY SENSOR ETC |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 |
| | WHICH REQUIRES THESE EVEN WHEN A |
| | SEPARATELY METERED TENANT. |
| | ** PLEASE KNOW, IF THIS TENANTS SPACE IS |
| | LESS THAN 5% OF THE TOTAL "BUILDING" SQ |
| | FOOTAGE THEN IT IS POSSIBLE THAT THIS |
| | SPACE MAY MEET AN EXCEPTION. |
| | ** PLEASE KNOW, THIS DOES NOT INCLUDE |
| | ANY LIGHTING FOR EM/NIGHT LTS WHICH ARE |
| | REQUIRED OR ON FOR "SAFETY". |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE FBC CHAPTER 13, |
| | 13-413.1.ABC.1.1, & .2. |
| | PLEASE PROVIDE SCHEDULING, CIRCUITING |
| | AND SPACE CONTROL DEVICES FOR OVERIDES |
| | AND SPACE CONTROL OVERIDE FOR SPACE. |
| | |
| | 3)NOTE: PLEASE SEE SEE ADDRESSING NEEDS |
| | TO BE CORRECTED. PLEASE SEE PERMIT |
| | APPLICATION MENTIONS 2060 ALONG WITH |
| | PLANS, HOWEVER THE PCN USED FOR |
| | APPLICATION CORRELATES TO OUR SYSTEM AND |
| | PAPA AS 2000 PALM BEACH LAKES. PLEASE |
| | SEE COMMENTS FROM ADDRESSING STOP AND |
| | ADJUST PLANS WHEN NEEDED OR APPLICATION. |
| | FAC 61G1-16.004 |
| | |
| | 4)NOTE:NO, PLEASE SEE ENERGY |
| | CALCULATIONS STILL ARE SEALED WITH |
| | "CERTIFICATE"?? PLEASE KNOW, THIS |
| | PROJECT HAS NOT BEEN SUBMITTED FOR |
| | PERMIT AND WAS NOT SUBMITTED FOR PERMIT |
| | BEFORE THE DEC 31ST, 2005 DATE. |
| | THEREFORE ALL SEALS MUST MEET THE |
| | REQUIREMENTS AS STATED IN THE FAC AND FS |
| | BELOW. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE ENERGY CALCUALTIONS |
| | CONTAINS THE SEAL WHICH INDICATES |
| | "CERTIFICATE" IN THE SAID SEAL OF THE |
| | ENGINEER OF RECORD. PLEASE SEE FAC |
| | 61G15-23.001 WHICH REQUIRED THE SEAL TO |
| | CHANGE FROM "CERTIFICATE" TO "LICENSE" |
| | AS OF FEB 5, 2004. PLEASE KNOW AND |
| | EXTENSION WAS GRANTED TO THE FINAL DATE |
| | OF 12/31/05. PLEASE KNOW, THE NEW SEAL |
| | MUST BE USED. |
| | ** PLANS ARE USING CORRECT SEAL. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: OK. |
| | |
| | 8) NOTE: OK. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE:OK. |
| | |
| | ************* NEW NOTE ************ |
| | |
| | |
| | 12) NOTE: PLEASE SEE MISSING REQUIRED ON |
| | TITLE BLOCKS FOR ARCHITECT AND FIRM AS |
| | SHOWN. |
| | PLEASE SEE FAC 61G1-16.004, AND FS |
| | 481.219. |
| | MISSING PRINTED NAME AND LICENSE #. |
| | MISSING THE FIRM LICENSE #, ALSO KNOWN |
| | AS THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER. |
| | PLEASE KNOW, THIS IS REQUIRED ON ALL |
| | SHEETS WHICH CONTAIN THIS TITLE BLOCK |
| | AND WHICH ARE SIGNED, DATED AND SEALED |
| | BY THE ARCHITECT. |
| | PLEASE KNOW, THIS IS REQUIRED FOR ALL |
| | TRADES WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEWER(S). |
| | ** PLEASE SEE ARCHITECT HAS NOT DATED |
| | PLANS AS REQUIRED PER FS 481.221 |
| | |
| | ** PLEASE BE AWARE OF ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONLY ONE SET OF ANY OLD/VOIDED REMOVED |
| | SHEETS NEED BE SUBMITTED BACK SEPARTELY |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMITTHE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |