Plan Review Notes
Plan Review Notes For Permit 06021049
Permit Number 06021049
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-30 00:00:00*** UNSAT ***
  
 ** PLEASE KNOW, PLANS ARE STILL ONLY
 BEING SUBMITTED FOR "'PLAN REVIEW** AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT TO
 DATE.
  
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW STILL APPLY. MOST WERE
 ADDRESSED.
 PLEASE KNOW, FS 553.80(2)(B) DOES NOT
 APPLY AS PLANS HAVE NOT BEEN SUBMITTED
 FOR PERMIT.
  
  
  
 1)NOTE:NO, PLEASE SEE PLANS/COVER
 SHEETS REFLECTS THE 2004 FBC FOR THE
 ELECTRICAL CODE. PLEASE REFERENCE THE
 2002 NFPA-70.
 PLEASE ALSO SEE ENERGY CALCULATIONS ARE
 STILL DESIGNED AND STATED PER 2001 FBC.
  
 ** PREVIOUS NOTE **
 PLEASE SEE PLANS REFERENCE THE
 2001 FBC AND OTHER CODES NO LONGER IN
 AFFECT. PLEASE KNOW, THE NEW 2004 FBC
 WAS ADOPTED ON OCT, 1ST, 2005.
 PLEASE ALSO SEE OTHER CODES NOTES WHICH
 ARE NO LONGER IN AFFECT. PLEASE
 REFERENCE THE FOLLOWING
 CODES. NFPA-70 2002, NFPA-101 2003,
 NFPA-72 2002.
  
  
 2)NOTE:NO, PLEASE SEE THIS NOTE WAS
 TYPED WITH THE "413" INSTEAD OF THE
 "415". THIS WAS IN ERROROF THIS
 OFFICE. THE NOTE WAS SHOWN ON PLANS FOR
 THE RESPONSE FROM THE DESIGNER INSTEAD
 OF OF PLACING ANY COMMENTS OR QUESTIONS
 IN A RESPONSE LETTER?
 PLEASE SEE THIS REQUIREMENT OF HAVING
 THE LIGHTING CONTROLS DOES APPLY AS
 STATED, IT IS IN A BUILDING LARGER THAN
 5K SQ FT. PLEASE SEE THAT THIS SPACE IS
 A SEPARATELY METERED SPACE ON THIS SAME
 ELECTRICAL SERVICE.
 PLEASE SEE THAT THE TC PROVIDED IS OK,
 HOWEVER AN OVER RIDE DEVICE IS REQUIRED
 AT THE ENTRANCE(S) TO SPACE WHERE THE
 OCCUPANT CAN READLITY SEE THE LIGHTING
 BEING CONTROLLED. THIS OVERRIDE(S)
 DEVICE IF TIMER CANE ONLY HAVE A SETTING
 OF 4HRS. PLEASE SEE ANY SEPARATE SPACES
 WITH FLR TO CEILING HEIGHT PARTITIONS
 SHALL ALSO CONTAIN AN DEVICE OF SOME
 SORT EITHER MOTION SENSOR, INFARED,
 OCCUPANCY SENSOR ETC
 PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1
 WHICH REQUIRES THESE EVEN WHEN A
 SEPARATELY METERED TENANT.
 ** PLEASE KNOW, IF THIS TENANTS SPACE IS
 LESS THAN 5% OF THE TOTAL "BUILDING" SQ
 FOOTAGE THEN IT IS POSSIBLE THAT THIS
 SPACE MAY MEET AN EXCEPTION.
 ** PLEASE KNOW, THIS DOES NOT INCLUDE
 ANY LIGHTING FOR EM/NIGHT LTS WHICH ARE
 REQUIRED OR ON FOR "SAFETY".
  
 ** PREVIOUS NOTE **
 PLEASE SEE FBC CHAPTER 13,
 13-413.1.ABC.1.1, & .2.
 PLEASE PROVIDE SCHEDULING, CIRCUITING
 AND SPACE CONTROL DEVICES FOR OVERIDES
 AND SPACE CONTROL OVERIDE FOR SPACE.
  
 3)NOTE: PLEASE SEE SEE ADDRESSING NEEDS
 TO BE CORRECTED. PLEASE SEE PERMIT
 APPLICATION MENTIONS 2060 ALONG WITH
 PLANS, HOWEVER THE PCN USED FOR
 APPLICATION CORRELATES TO OUR SYSTEM AND
 PAPA AS 2000 PALM BEACH LAKES. PLEASE
 SEE COMMENTS FROM ADDRESSING STOP AND
 ADJUST PLANS WHEN NEEDED OR APPLICATION.
 FAC 61G1-16.004
  
 4)NOTE:NO, PLEASE SEE ENERGY
 CALCULATIONS STILL ARE SEALED WITH
 "CERTIFICATE"?? PLEASE KNOW, THIS
 PROJECT HAS NOT BEEN SUBMITTED FOR
 PERMIT AND WAS NOT SUBMITTED FOR PERMIT
 BEFORE THE DEC 31ST, 2005 DATE.
 THEREFORE ALL SEALS MUST MEET THE
 REQUIREMENTS AS STATED IN THE FAC AND FS
 BELOW.
  
 ** PREVIOUS NOTE **
 PLEASE SEE ENERGY CALCUALTIONS
 CONTAINS THE SEAL WHICH INDICATES
 "CERTIFICATE" IN THE SAID SEAL OF THE
 ENGINEER OF RECORD. PLEASE SEE FAC
 61G15-23.001 WHICH REQUIRED THE SEAL TO
 CHANGE FROM "CERTIFICATE" TO "LICENSE"
 AS OF FEB 5, 2004. PLEASE KNOW AND
 EXTENSION WAS GRANTED TO THE FINAL DATE
 OF 12/31/05. PLEASE KNOW, THE NEW SEAL
 MUST BE USED.
 ** PLANS ARE USING CORRECT SEAL.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE:OK.
  
 ************* NEW NOTE ************
  
  
 12) NOTE: PLEASE SEE MISSING REQUIRED ON
 TITLE BLOCKS FOR ARCHITECT AND FIRM AS
 SHOWN.
 PLEASE SEE FAC 61G1-16.004, AND FS
 481.219.
 MISSING PRINTED NAME AND LICENSE #.
 MISSING THE FIRM LICENSE #, ALSO KNOWN
 AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER.
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 SHEETS WHICH CONTAIN THIS TITLE BLOCK
 AND WHICH ARE SIGNED, DATED AND SEALED
 BY THE ARCHITECT.
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
 ** PLEASE SEE ARCHITECT HAS NOT DATED
 PLANS AS REQUIRED PER FS 481.221
  
 ** PLEASE BE AWARE OF ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE SET OF ANY OLD/VOIDED REMOVED
 SHEETS NEED BE SUBMITTED BACK SEPARTELY
 FOR REFERENCE.
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]