Plan Review Notes
Plan Review Notes For Permit 06021049
Permit Number 06021049
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-18 00:00:00****CORRECTIONS****
 ****MAJOR WORKING DRAWING REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)DECLARE OCCUPANCY, FBC CHAPTER 3.
  
 3.)SIGN OWNER/AGENT LINE OF ENERGY
 CALC, FBC13-103.1.
  
 4.)THE SEAL FOR THE ARCHITECT IS TO BE
 DATED, FAC61G1-16.
  
 5.)THE SEAL FOR THE ENGINEER IS
 EXPIRED, FAC61G15-23. (ENERGY CALCS)
  
 6.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ARCHITECT FIRM IS TO BE
 ON EACH SHEET, FAC61G1-16.003, 004.
  
 7.)THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS TO BE ON EACH
 SHEET, FAC61G1-16.003, 004.
  
 8.)GOVERNING CODES ARE FBC2004,
 FBC2004 EXISTING BUILDING CODE.
  
 9.)THE PLAN STATES THAT THE BUILDING
 DEPARTMENT IS PALM BEACH COUNTY, SHOULD
 STATE CITY OF WEST PALM BEACH.
  
 10.)ADDRESSED.
  
 11.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING; HEIGHT, AREA,
 MINIMUM BUILDING TYPE FBC6, SPRINKLED OR
 UNSPRINKLED.IF THE BUILDING IS
 REQUIRED TO BE SPRINKLED, FIRE SPRINKLER
 PLANS REQUIRED.
  
 12.)SHOW THE REQUIRED CLEAR FLOOR
 SPACE AT THE SINKS, MEN?S TOILET AND
 WOMEN?S TOILET, FBC11-4.24.5.
  
 13.)SHOW ACCESS AISLES, FBC11-5.3.
  
 14.)PROVIDE THE HEIGHT OF THE POS
 AREA, A1.2, FBC11-7.2.
  
 15.)SHOW MANEUVERING CLEARANCE, DOOR
 5, FBC11 FIGURE 25, FBC11-4.13.6.
  
 16.)DOORS 5 AND 6, SHOW COMPLIANCE
 WITH FBC1008.1.8.8, LEAVE UNOBSTRUCTED
 HALF THE REQUIRED WIDTH.
  
 NEW COMMENTS:
  
 17.)ENERGY CALCS ARE TO BE FBC2004.
  
 18.)DECLARE OCCUPANT LOAD.COVER
 SHEET SHOWS SEATING OF 44, WHAT ABOUT
 EMPLOYEES?
  
 19.)SHOW TRAVEL DISTANCE.PLANS STATE
 THAT ONE EXIT IS REQUIRED.TWO ARE
 SHOWN, BUT PLANS HAVE NOW BEEN REVISED
 SO THAT DOORS 3 AND 4 DO NOT COMPLY WITH
 FBC1008.1.1.8.ADDRESS.
  
 20.)DECLARE LEVEL OF ALTERATION, FBC
 EB CHAPTER 3.