| 2006-05-06 00:00:00 | |
| | FBC 2004 PLUMBING CODE PLAN REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | UNSAT |
| | |
| | 1) SHT P-2 GRASE TRAP TO BE SIZED BY |
| | W P BEACHWATERPLANT LAB SUPERVISOR |
| | INDUSTRIAL COORDINATOR, LYNN MASSON |
| | OFFICE 561-822-2271 |
| | E-MAIL [email protected] |
| | |
| | 2) SHT P-2 PLANS SHALL BE ROUTED TO DBPR |
| | BUSINESS AND HOTEL DIVISION FOR |
| | REVIEW. MINIMUM 2 SETS OF PLANS |
| | SHALL BE REVIEWED AND STAMPED |
| | AND THE TWO PAGE ?WORKSHEETS? |
| | ATTACHED TO EACH SET OF PLANS |
| | PRIOR TO RESUBMITTING TO CITY OF WEST |
| | PALM BEACH |
| | FOR REVIEW. PLEASE CONTACT DBPR |
| | AT (850) 487-1395. |
| | |
| | 3) SHT A-1.0 REST ROOMS DOORS |
| | 11-4.22.2 DOORS.ALL DOORS TO ACCESSIBLE |
| | TOILET ROOMS SHALL COMPLY WITH SECTION |
| | 11-4.13. DOORS SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE REQUIRED FOR ANY |
| | FIXTURE. |
| | |
| | 4)SHT P-3 GAS RISER DIAGRAM |
| | SEE GAS PLAN REVIEW COMMENTS. |
| | |
| | 5) SHT P-3 PLUMBING SPECIFICATIONS NOTE |
| | (8)REFERENCE TO AIR CHAMBERS PROVIDE A |
| | DETAIL COMPLYING WITH PRI STD-WH 201 |
| | ALL AIR CHAMBERS SHALL BE ACCESSIBLE. |
| | |
| | 6) SHT P-2 WATER HEATER |
| | 607.3 THERMAL EXPANSION CONTROL. |
| | A MEANS OF CONTROLLING INCREASED |
| | PRESSURE CAUSED BY THERMAL EXPANSION |
| | SHALL BE PROVIDED WHERE REQUIRED IN |
| | ACCORDANCE WITH SECTIONS 607.3.1 AND |
| | 607.3.2. |
| | 607.3.2 BACKFLOW PREVENTION DEVICE OR |
| | CHECK VALVE. |
| | WHERE A BACKFLOW PREVENTION DEVICE, |
| | CHECK VALVE OR OTHER DEVICE IS INSTALLED |
| | ON A WATER SUPPLY SYSTEM UTILIZING |
| | STORAGE WATER HEATING EQUIPMENT SUCH |
| | THAT THERMAL EXPANSION CAUSES AN |
| | INCREASE IN PRESSURE, A DEVICE FOR |
| | CONTROLLING PRESSURE SHALL BE INSTALLED. |
| | |
| | 7) SHT P-3 WATER RISER |
| | 604.9 WATER HAMMER. |
| | THE FLOW VELOCITY OF THE WATER |
| | DISTRIBUTION SYSTEM SHALL BE CONTROLLED |
| | TO REDUCE THE POSSIBILITY OF WATER |
| | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE |
| | INSTALLED WHERE QUICK-CLOSING VALVES ARE |
| | UTILIZED. WATER-HAMMER ARRESTORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S SPECIFICATIONS. |
| | WATER-HAMMER ARRESTORS SHALL CONFORM TO |
| | ASSE 1010. |
| | SHALL BE INSTALLED BETWEEN THE LAST TWO |
| | FIXTURES, NOT AT THE TOP OF THE RISER. |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |