2006-05-06 00:00:00 
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 UNSAT
  
 1) SHT P-2 GRASE TRAP TO BE SIZED BY
 W P BEACHWATERPLANT LAB SUPERVISOR
 INDUSTRIAL COORDINATOR, LYNN MASSON
 OFFICE 561-822-2271
 E-MAIL [email protected]
  
 2) SHT P-2 PLANS SHALL BE ROUTED TO DBPR
 BUSINESS AND HOTEL DIVISION FOR
 REVIEW. MINIMUM 2 SETS OF PLANS
 SHALL BE REVIEWED AND STAMPED
 AND THE TWO PAGE ?WORKSHEETS?
 ATTACHED TO EACH SET OF PLANS
 PRIOR TO RESUBMITTING TO CITY OF WEST
 PALM BEACH
 FOR REVIEW. PLEASE CONTACT DBPR
 AT (850) 487-1395.
  
 3) SHT A-1.0 REST ROOMS DOORS
 11-4.22.2 DOORS.ALL DOORS TO ACCESSIBLE
 TOILET ROOMS SHALL COMPLY WITH SECTION
 11-4.13. DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
  
 4)SHT P-3 GAS RISER DIAGRAM
 SEE GAS PLAN REVIEW COMMENTS.
  
 5) SHT P-3 PLUMBING SPECIFICATIONS NOTE
 (8)REFERENCE TO AIR CHAMBERS PROVIDE A
 DETAIL COMPLYING WITH PRI STD-WH 201
 ALL AIR CHAMBERS SHALL BE ACCESSIBLE.
  
 6) SHT P-2 WATER HEATER
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
 607.3.2 BACKFLOW PREVENTION DEVICE OR
 CHECK VALVE.
 WHERE A BACKFLOW PREVENTION DEVICE,
 CHECK VALVE OR OTHER DEVICE IS INSTALLED
 ON A WATER SUPPLY SYSTEM UTILIZING
 STORAGE WATER HEATING EQUIPMENT SUCH
 THAT THERMAL EXPANSION CAUSES AN
 INCREASE IN PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED.
  
 7) SHT P-3 WATER RISER
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED
 TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010.
 SHALL BE INSTALLED BETWEEN THE LAST TWO
 FIXTURES, NOT AT THE TOP OF THE RISER.
  
 END OF COMMENTS, QUESTIONS 561-805-6692