Plan Review Notes
Plan Review Notes For Permit 06021049
Permit Number 06021049
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-04-20 00:00:00******DENIED******
 PLAN REVIEW ONLY
  
 1) BUILDING DATA INDICATES THAT BUILDING
 IS NOT SPRINKLERED, BUT RESPONSIBILITY
 SCHEDULE INDICATES SPRINKLER SYSTEM.
 PLEASE CLARIFY.
  
 2) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING IN TERMS OF CLASS A,B ORC.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHER(S)
 REQUIRED AND SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED 75' TRAVEL
 DISTANCE REQUIREMENT. "K" TYPE
 EXTINGUISHER REQUIRED IN KITCHEN.
  
 4) PLEASE SEE ELECTRICAL REVIEW COMMENT
 REGARDING CODE EDITIONS AND MAKE
 APPROPRIATE CORRECTIONS. NFPA 101 AND
 NFPA 1, 2003 EDITIONS.
  
 5) IF NO FIRE ALARM SYSTEM, HOOD
 SUPPRESSION WILL BE REQUIRED TO DISPLAY
 OCCUPANT NOTIFICATION BY WAY OF
 AUDIBLE/VISUAL DEVICE. SYSTEM TO BE TIED
 INTO FIRE ALARM SYSTEM IF APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722