| Plan Review Notes For Permit 06021049 |
| Permit Number |
06021049 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-20 00:00:00 | ******DENIED****** | | | PLAN REVIEW ONLY | | | | | | 1) BUILDING DATA INDICATES THAT BUILDING | | | IS NOT SPRINKLERED, BUT RESPONSIBILITY | | | SCHEDULE INDICATES SPRINKLER SYSTEM. | | | PLEASE CLARIFY. | | | | | | 2) PLEASE INDICATE MINIMUM INTERIOR | | | FINISH CLASSIFICATION FOR WALLS AND | | | CEILING IN TERMS OF CLASS A,B ORC. | | | | | | 3) 2A-10B,C RATED FIRE EXTINGUISHER(S) | | | REQUIRED AND SHALL BE MOUNTED AT | | | DISTANCES NOT TO EXCEED 75' TRAVEL | | | DISTANCE REQUIREMENT. "K" TYPE | | | EXTINGUISHER REQUIRED IN KITCHEN. | | | | | | 4) PLEASE SEE ELECTRICAL REVIEW COMMENT | | | REGARDING CODE EDITIONS AND MAKE | | | APPROPRIATE CORRECTIONS. NFPA 101 AND | | | NFPA 1, 2003 EDITIONS. | | | | | | 5) IF NO FIRE ALARM SYSTEM, HOOD | | | SUPPRESSION WILL BE REQUIRED TO DISPLAY | | | OCCUPANT NOTIFICATION BY WAY OF | | | AUDIBLE/VISUAL DEVICE. SYSTEM TO BE TIED | | | INTO FIRE ALARM SYSTEM IF APPLICABLE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|