| Date |
Text |
| 2006-03-29 00:00:00 | ***** UNSAT ******** |
| | |
| | ** PLEASE KNOW, PLANS WERE SUBMITTED FOR |
| | "PLAN REVIEW" ONLY AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. |
| | |
| | |
| | 1)NOTE: PLEASE SEE PLANS REFERENCE THE |
| | 2001 FBC AND OTHER CODES NO LONGER IN |
| | AFFECT. PLEASE KNOW, THE NEW 2004 FBC |
| | WAS ADOPTED ON OCT, 1ST, 2005. |
| | PLEASE ALSO SEE OTHER CODES NOTES WHICH |
| | ARE NO LONGER IN AFFECT. PLEASE |
| | REFERENCE THE FOLLOWING |
| | CODES. NFPA-70 2002, NFPA-101 2003, |
| | NFPA-72 2002. |
| | |
| | |
| | 2)NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-413.1.ABC.1.1, & .2. |
| | PLEASE PROVIDE SCHEDULING, CIRCUITING |
| | AND SPACE CONTROL DEVICES FOR OVERIDES |
| | AND SPACE CONTROL OVERIDE FOR SPACE. |
| | |
| | 3)NOTE: PLEASE SEE SEE ADDRESSING NEEDS |
| | TO BE CORRECTED. PLEASE SEE PERMIT |
| | APPLICATION MENTIONS 2060 ALONG WITH |
| | PLANS, HOWEVER THE PCN USED FOR |
| | APPLICATION CORRELATES TO OUR SYSTEM AND |
| | PAPA AS 2000 PALM BEACH LAKES. PLEASE |
| | SEE COMMENTS FROM ADDRESSING STOP AND |
| | ADJUST PLANS WHEN NEEDED OR APPLICATION. |
| | FAC 61G1-16.004 |
| | |
| | 4)NOTE:PLEASE SEE ENERGY CALCUALTIONS |
| | CONTAINS THE SEAL WHICH INDICATES |
| | "CERTIFICATE" IN THE SAID SEAL OF THE |
| | ENGINEER OF RECORD. PLEASE SEE FAC |
| | 61G15-23.001 WHICH REQUIRED THE SEAL TO |
| | CHANGE FROM "CERTIFICATE" TO "LICENSE" |
| | AS OF FEB 5, 2004. PLEASE KNOW AND |
| | EXTENSION WAS GRANTED TO THE FINAL DATE |
| | OF 12/31/05. PLEASE KNOW, THE NEW SEAL |
| | MUST BE USED. |
| | ** PLANS ARE USING CORRECT SEAL. |
| | |
| | 5)NOTE: PLEASE LOAD CALCUALTIONS FOR |
| | EXISTING SERVICE AND NEW LOADS ADDED TO |
| | EXISTING. |
| | 215.5, 220, |
| | |
| | 6) NOTE: PLEASE INDICATE ALL CONTINUOUS |
| | LOADS AT 125%. |
| | 215.3,230.42 |
| | |
| | 7) NOTE: PLEASE PROVIDE GFI PROTECTION |
| | PER 2002 NEC, 210.8B3 |
| | |
| | 8) NOTE: PLEASE SUBMIT ALL AIC RATINGS |
| | FOR ALL NEW MAINS/ SERVICE EQUIPMENT. |
| | 110.9,215.5 |
| | |
| | 8)NOTE: PLEASE PROVIDE |
| | NOTE/IDENTIFICATION OF "FEED-THRU" LUGS |
| | IF INDEED THIS IS THE METHOD OF FEDDING |
| | PANEL "B". |
| | 215.5 |
| | |
| | 9) NOTE: PLEASE INDICATE THE |
| | "FLOATING/ISOLATED" NEUTRAL IN METER AS |
| | THIS LOCAITON IS NOT THE FIRST MEANS OF |
| | DISCONNECT FOR SERVICE. |
| | 250.6,250.24B |
| | |
| | 10) NOTE: PLEASE CLARIFY CIRCUTING, |
| | PLEASE SEE SOME CIRCUITS DO NOT SEEM TO |
| | CORRELATE WITH PLANS? |
| | "SHOW WINDOWS?" |
| | 215.5 |
| | |
| | 11) NOTE: PLEASE SEE 210.62, 220.12A FOR |
| | MIN RECEPTS REQUIRED FOR WINDOW SPACING. |
| | PLEASE SEE PLANS INDICATE A "SIGN" |
| | ALREADY FOR THE WINDOW RECEPT AS |
| | DEDICATED. ADDITIONAL RECEPTS WOULD BE |
| | REQUIRED ALONG WITH ADDITIONAL RECEPTS |
| | FOR THE LINEAR FT SHOWN MORE THAN 12'. |
| | |
| | ** PLEASE BE AWARE OF ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONLY ONE SET OF ANY OLD/VOIDED REMOVED |
| | SHEETS NEED BE SUBMITTED BACK SEPARTELY |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMITTHE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |