Plan Review Notes
Plan Review Notes For Permit 06021049
Permit Number 06021049
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-29 00:00:00***** UNSAT ********
  
 ** PLEASE KNOW, PLANS WERE SUBMITTED FOR
 "PLAN REVIEW" ONLY AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE SEE PLANS REFERENCE THE
 2001 FBC AND OTHER CODES NO LONGER IN
 AFFECT. PLEASE KNOW, THE NEW 2004 FBC
 WAS ADOPTED ON OCT, 1ST, 2005.
 PLEASE ALSO SEE OTHER CODES NOTES WHICH
 ARE NO LONGER IN AFFECT. PLEASE
 REFERENCE THE FOLLOWING
 CODES. NFPA-70 2002, NFPA-101 2003,
 NFPA-72 2002.
  
  
 2)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-413.1.ABC.1.1, & .2.
 PLEASE PROVIDE SCHEDULING, CIRCUITING
 AND SPACE CONTROL DEVICES FOR OVERIDES
 AND SPACE CONTROL OVERIDE FOR SPACE.
  
 3)NOTE: PLEASE SEE SEE ADDRESSING NEEDS
 TO BE CORRECTED. PLEASE SEE PERMIT
 APPLICATION MENTIONS 2060 ALONG WITH
 PLANS, HOWEVER THE PCN USED FOR
 APPLICATION CORRELATES TO OUR SYSTEM AND
 PAPA AS 2000 PALM BEACH LAKES. PLEASE
 SEE COMMENTS FROM ADDRESSING STOP AND
 ADJUST PLANS WHEN NEEDED OR APPLICATION.
 FAC 61G1-16.004
  
 4)NOTE:PLEASE SEE ENERGY CALCUALTIONS
 CONTAINS THE SEAL WHICH INDICATES
 "CERTIFICATE" IN THE SAID SEAL OF THE
 ENGINEER OF RECORD. PLEASE SEE FAC
 61G15-23.001 WHICH REQUIRED THE SEAL TO
 CHANGE FROM "CERTIFICATE" TO "LICENSE"
 AS OF FEB 5, 2004. PLEASE KNOW AND
 EXTENSION WAS GRANTED TO THE FINAL DATE
 OF 12/31/05. PLEASE KNOW, THE NEW SEAL
 MUST BE USED.
 ** PLANS ARE USING CORRECT SEAL.
  
 5)NOTE: PLEASE LOAD CALCUALTIONS FOR
 EXISTING SERVICE AND NEW LOADS ADDED TO
 EXISTING.
 215.5, 220,
  
 6) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125%.
 215.3,230.42
  
 7) NOTE: PLEASE PROVIDE GFI PROTECTION
 PER 2002 NEC, 210.8B3
  
 8) NOTE: PLEASE SUBMIT ALL AIC RATINGS
 FOR ALL NEW MAINS/ SERVICE EQUIPMENT.
 110.9,215.5
  
 8)NOTE: PLEASE PROVIDE
 NOTE/IDENTIFICATION OF "FEED-THRU" LUGS
 IF INDEED THIS IS THE METHOD OF FEDDING
 PANEL "B".
 215.5
  
 9) NOTE: PLEASE INDICATE THE
 "FLOATING/ISOLATED" NEUTRAL IN METER AS
 THIS LOCAITON IS NOT THE FIRST MEANS OF
 DISCONNECT FOR SERVICE.
 250.6,250.24B
  
 10) NOTE: PLEASE CLARIFY CIRCUTING,
 PLEASE SEE SOME CIRCUITS DO NOT SEEM TO
 CORRELATE WITH PLANS?
 "SHOW WINDOWS?"
 215.5
  
 11) NOTE: PLEASE SEE 210.62, 220.12A FOR
 MIN RECEPTS REQUIRED FOR WINDOW SPACING.
 PLEASE SEE PLANS INDICATE A "SIGN"
 ALREADY FOR THE WINDOW RECEPT AS
 DEDICATED. ADDITIONAL RECEPTS WOULD BE
 REQUIRED ALONG WITH ADDITIONAL RECEPTS
 FOR THE LINEAR FT SHOWN MORE THAN 12'.
  
 ** PLEASE BE AWARE OF ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE SET OF ANY OLD/VOIDED REMOVED
 SHEETS NEED BE SUBMITTED BACK SEPARTELY
 FOR REFERENCE.
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]