2006-05-08 00:00:00****CORRECTIONS****
 ****MAJOR WORKING DRAWING REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)DECLARE OCCUPANCY, FBC CHAPTER 3.
  
 3.)SIGN OWNER/AGENT LINE OF ENERGY
 CALC, FBC13-103.1
  
 4.)THE SEAL FOR THE ARCHITECT IS TO BE
 DATED, FAC61G1-16.
  
 5.)THE SEAL FOR THE ENGINEER IS
 EXPIRED, FAC61G15-23.
  
 6.)THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ARCHITECT FIRM IS TO BE
 ON EACH SHEET, FAC61G1-16.003, 004.
  
 7.)THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS TO BE ON EACH
 SHEET, FAC61G1-16.003, 004.
  
 8.)GOVERNING CODES ARE FBC2004,
 FBC2004 EXISTING BUILDING CODE.
  
 9.)THE PLAN STATES THAT THE BUILDING
 DEPARTMENT IS PALM BEACH COUNTY, SHOULD
 STATE CITY OF WEST PALM BEACH.
  
 10.)HANDICAP CODE REFERS TO DADE
 COUNTY, GOVERNING ACCESSIBILITY CODE IS
 FBC2004 CHAPTER 11.
  
 11.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING; HEIGHT, AREA,
 MINIMUM BUILDING TYPE FBC6, SPRINKLED OR
 UNSPRINKLED.IF THE BUILDING IS
 REQUIRED TO BE SPRINKLED, FIRE SPRINKLER
 PLANS REQUIRED.
  
 12.)SHOW THE REQUIRED CLEAR FLOOR
 SPACE AT THE SINKS, MEN?S TOILET AND
 WOMEN?S TOILET, FBC11-4.24.5.
  
 13.)SHOW ACCESS AISLES, FBC11-5.3.
  
 14.)PROVIDE THE HEIGHT OF THE POS
 AREA, A1.2, FBC11-7.2.
  
 15.)SHOW MANEUVERING CLEARANCE, DOOR
 5, FBC11 FIGURE 25, FBC11-4.13.6.
  
 16.)DOORS 5 AND 6, SHOW COMPLIANCE
 WITH FBC1008.1.8.8, LEAVE UNOBSTRUCTED
 HALF THE REQUIRED WIDTH.
  