| 2006-05-24 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | COMMENTS FROM PREVIOUS LIST, NUMBERING |
| | REMIANING THE SAME FOR CONSISTENCY |
| | |
| | 2.)COMPLETE THE ATTACHED INSTALLATION |
| | SCHEDULE OR PROVIDE REQUIRED INFORMATION |
| | IN A SIMILAR FORMAT.YOU MAY SHOW |
| | ANCHOR SPACING BY CIRCLING IT ON THE |
| | PRODUCT APPROVAL. |
| | |
| | PROVIDE LEGIBLE PRODUCT APPROVALS.I |
| | CANNOT READ THE FASTENER INFORMATION. |
| | |
| | 5.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL, FAC9B72, |
| | WWW.FLORIDABUILDING.ORG.IF A STATE |
| | PRODUCT APPROVAL IS NOT AVAILABLE, |
| | PLEASE ADVISE AND A LOCAL WILL BE ISSUED |
| | USING THE NOA. |
| | |
| | 6.)ON THE PRODUCT APPROVAL, MARK WHICH |
| | DETAILS APPLY TO THIS JOB.USE INK |
| | RATHER THAN A HIGHLIGHTER. |
| | |
| | 7.)SHOW THE EMERGENCY MEANS OF ESCAPE, |
| | FBC R310.THE FLOOR PLAN SHOWS A DOOR |
| | BUT DOES NOT INDICATE WHETHER OR NOT |
| | THIS WILL BE SHUTTERED.THIS CAN BE |
| | DONE WITH A NOTE ON THE PLAN. |
| | |
| | 11.)SEE ATTACHED POLICY REGARDING |
| | MISSILE IMPACT PROTECTION.SEE ITEM |
| | #13.SUBMIT AN INSTALLATION PLAN. |
| | REMOVABLE SHUTTES ARE ALLOWED ON THE |
| | FIRST FLOOOR ONLY AFTER AN INSTALLATION |
| | PLAN HAS BEEN APPROVED BY THE BUILDING |
| | OFFICIAL.PLEASE SUBMIT A PLAN FOR |
| | REVIEW. THIS SHOULD BE DONE PRIOR TO |
| | RESUBMITTAL OF THE PLAN AND CAN BE DONE |
| | VIA EMAIL TO [email protected] ORIGINAL |
| | WILL BE REQUIRED AFTER THE PRELIMINARY |
| | REVIEW IS COMPLETE. |