| 2006-05-08 00:00:00 | ***REVISED LIST 5/8/6*** |
| | |
| | |
| | **************************************** |
| 2006-03-19 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2004 |
| | |
| | SHUTTER PERMIT APPLICATION, ONLY CHECKED |
| | ITEMS APPLY |
| | |
| | _XX_1.A NOTICE OF COMMENCEMENT MUST |
| | BE FILED WITH THE CLERK OF COURTS BEFORE |
| | A PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | _XX_2.PROVIDE BUILDING HEIGHT. |
| | DESIGN PRESSURES FOR BUILDINGS OVER |
| | 60FEET ARE REQUIRED TO BE DESIGNED USING |
| | ASCE7, FBC1609.1.1. DOCUMENTS PREPARED |
| | BY AN ENGINEER AND SUBMITTED FOR PUBLIC |
| | RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| | FAC61G15-23.002. |
| | |
| | ____3.PROVIDE A COPY OF THE CONDO |
| | ASSOCIATION APPROVAL. |
| | |
| | _XX_4.COMPLETE THE ATTACHED |
| | INSTALLATION SCHEDULE OR PROVIDE |
| | REQUIRED INFORMATION IN A SIMILAR |
| | FORMAT.YOU MAY SHOW ANCHOR SPACING BY |
| | CIRCLING IT ON THE APPROPRIATE CHARTS ON |
| | THE PRODUCT APPROVAL. |
| | |
| | _XX_5.FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED, FAC9B72, |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | _XX_6.ON THE PRODUCT APPROVAL, MARK |
| | WHICH DETAILS APPLY TO THIS JOB.PLEASE |
| | USE INK RATHER THAN A HIGHLIGHTER. |
| | |
| | _XX_7.SHOW THE EMERGENCY MEANS OF |
| | ESCAPE, FBC R310. |
| | |
| | _XX_8.PROVIDE A FLOOR PLAN SHOWING |
| | WHERE THE SHUTTERS WILL BE INSTALLED |
| | WHICH CORRELATES WITH THE INSTALLATION |
| | SCHEDULE, ITEM 4 ABOVE. |
| | |
| | _XX_9.IS THIS SINGLE FAMILY OR |
| | MULTIFAMILY? |
| | |
| | WINDOW OR DOOR PERMIT APPLICATION, ONLY |
| | CHECKED ITEMS APPLY |
| | |
| | _XX_ 10.FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED, FAC9B72, |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | _XX_ 11.SEE ATTACHED POLICY REGARDING |
| | MISSILE IMPACT PROTECTION.SEE ITEM |
| | #13.SUBMIT AN INSTALLATION PLAN. |
| | REMOVABLE SHUTTERS ARE ALLOWED ON THE |
| | FIRST FLOOR ONLY AFTER AN INSTALLATION |
| | PLAN HAS BEEN APPROVED BY THE BUILDING |
| | OFFICIAL.REMOVABLE SHUTTERS NOT |
| | ALLOWED ON THE SECOND FLOOR. |