| 2006-03-07 00:00:00 | DENIED; |
| | 1.SANITARY RISER DIAGRAM, AUTOMATIC |
| | CLOTHES WASHER DRAIN TO BE 3" PER. |
| | FBC-2004 PLUMBING SEC. 406.3. |
| | 2.TABLE 403.1.3(E) MINIMUM PLUMBING |
| | FIXTURES. TWO DRINKING FOUNTAINS ARE |
| | REQUIRED. |
| | 3.WATER RISER DIAGRAM, WATER HAMMER |
| | ARRESTORS ARE REQURED ON THE AUTOMATIC |
| | CLOTHES WASHERS AND ON KITCHEN SINK SEC. |
| | 604.9. PLEASE SHOW ON PLANS. |
| | 4.WATER HEATER DETAIL SHOWS A |
| | RECIRCULATION PUMP, WATER RISER DOES NOT |
| | SHOW REQUIRED PIPING. PLEASE CORRECT. |
| | 5.SHOW SIZING CALCULATIONS FOR WATER |
| | SEVICE, SEE APPENDIX E. |
| | 6.HANDICAP BATHROOM FACILITIES ARE |
| | REQUIRED FOR CHILDREN AGES 2 THRU 5. |
| | PLEASE SHOW ON DETAIL AND ON FLOOR PLAN. |
| | SHOW CLEAR FLOOR SPACE, TURNING RADIUS, |
| | DOOR SWING, AND GRAB BARS. FOR |
| | REQUIREMENTS GO ON LINE TO: |
| | HTTP://WWW.ACCESS-BOARD.GOV/INDEXES/PUBS |
| | TTP://WWW.ACCESS-BOARD.GOV/INDEXES/PUBSI |
| | TP://WWW.ACCESS-BOARD.GOV/INDEXES/PUBSIN |
| | P://WWW.ACCESS-BOARD.GOV/INDEXES/PUBSIND |
| | ://WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDE |
| | //WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX |
| | /WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX. |
| | WWW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX.H |
| | WW.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX.HT |
| | W.ACCESS-BOARD.GOV/INDEXES/PUBSINDEX.HTM |
| | 7.THE SINKNEXT TO THE REF. IN |
| | KITCHENETTE MUST COMPLY WITH FBC-2004 |
| | CHAPTER 11 SEC. 11-4.23.3 KNEE CLEARENCE |
| | UNDER SINK. DOORS MUST BE REMOVED FOR |
| | FRONTAL APPROACH |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |
| | 805-6695 |