| Plan Review Notes For Permit 06021026 |
| Permit Number |
06021026 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-06 00:00:00 | DENIED: | | | | | | 1) SHALL COMPLY WITH NFPA 101 LIFE | | | SAFETY CODE, 2003 EDITION AND NFPA 1 | | | UNIFORM FIRE CODE, 2003 EDITION. | | | | | | 2) BASE ON SECTION 16.1.4.1 GENERAL. | | | OCCUPANCIES THAT INCLUDE PART-DAY | | | PRESCHOOLS, KINDERGARTENS, AND OTHER | | | SCHOOLS WHOSE PURPOSE IS PRIMARILY | | | EDUCATIONAL, EVEN THOUGH THE CHILDREN | | | WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL | | | AGE, SHALL COMPLY WITH THE PROVISIONS OF | | | CHAPTER 14. UNDER CHAPTER 14 NEW | | | EDUCATIONAL OCCUPANCIES REQUIRES THE | | | WIDTH OF THE CORRIDORS TO BE MINIMUM OF | | | SIX (6) FEET (72") WIDE. | | | | | | 3) PLEASE REFER CHAPTER 14 OF NFPA 101 | | | LIFE SAFETY CODE, 2003 EDITION FOR OTHER | | | REQUIREMENTS. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMIT | | | APPLICATIONS ARE REQUIRED FOR FIRE ALARM | | | AND FIRE SPRINKLER SYSTEMS REMODEL. | | | | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|