| 2006-02-24 00:00:00 | | | | 1} PLEASE INDICATE COMPLIANCE WITH | | | CHAPTER 13 OF THE FBC REGARDING ENERGY | | | CODES. | | | SEE 13-413,414 AND 415. | | | | | | 2} PLEASE SHOW CIRCUITING FOR THE EXIT | | | AND EMERGENCY LIGHTS IN COMPLIANCE WITH | | | 700.12(E) NEC. | | | | | | 3} INDICATE GUTTER SIZE IN COMPLIANCE | | | WITH ARTICLE 376. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|