Plan Review Notes
Plan Review Notes For Permit 06021026
Permit Number 06021026
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-15 00:00:00DENIED
  
 1) PROJECT INVOLVES A CHANGE OF
 OCCUPANCY. THE PLANS WILL NEED TO BE
 REVIEWED BY PALM BEACH COUNTY TO
 DETERMINE IF ANY IMPACT FEES ARE DUE.
 BOTH SETS OF PLANS ARE REQUIRED TO BE
 REVIEWED AND STAMPED BY THE COUNTY AND A
 COPY OF THE IMPACT FEE RECIEPT TO BE
 SUBMITTTED FOR PERMIT.
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SPECIFY THE CONSTRUCTION TYPE OF THE
 EXISTING STRUCTURE BASED ON FBC 2004
 DESIGNATIONS. SEE FBC 602.
  
 4) SPECIFY THE NUMBER OF STORIES. SEE
 FBC CHAPTER 50O.
  
 5) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT THE
 COVERSHEETS WITH THE FL# FOR THE
 EXTERIOR DOOR.
  
 6) SUBMIT FIRE SPRINKLER PLANS PER FBC
 106.3.5.
  
 7) FBC 436.7 REQUIRES A FIRE ALARM
 SYSTEM.
  
 8) FBC 436.7.1.2 REQUIRES FIRE ALARM
 SYSTEM TO TRANSMIT AUTOMATICALLY TO THE
 FIRE DEPARTMENT.
  
 9) FBC 436.7.2 REQUIRES A SMOKE
 DETECTION SYSTEM INSTALLED IN ACCORDANCE
 WITH NFPA 72.
  
 10) FBC 436.8 STATES THAT EVERY INTERIOR
 CORRIDOR SHALL BE CONSTRUCTED OF WALLS
 HAVING NOT LESS THAN A ONE HOUR
 FIRE-RESISTANCE RATING. EXCEPTIONS APPLY
 FOR APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEMS.
  
 11) FBC 1033.6 EVERY ROOM OR SPACE
 NORMALLY SUBJECT TO CLIENT OCCUPANCY,
 OTHER THAN BATHROOMS, SHALL HAVE AT
 LEAST ONE OUTSIDE WINDOW FOR EMERGENCY
 RESCUE AND VENTILATION. SEE EXCEPTIONS.
  
 12) FOR THE PURPOSE OF DETERMINING MEANS
 OF EGRESS REQUIREMENTS FBC 1004.1.2
 REQUIRES 20 NET SQUARE FEET PER OCCUPANT
 FOR DAY CARE OCCUPANCIES.
  
 13) SPECIFY THE SIZES OF EXISTING EXIT
 DOORS. SEE FBC 1008.1 AND 1008.1.1.
  
 14) THE EXIT DISCHARGE EGRESS COURT AT
 THE REAR SHALL COMPLY WITH FBC 1023.5.
  
 15) THE GATES AT THE EGRESS COURT SHALL
 COMPLY WITH FBC 1008.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  