| Plan Review Notes For Permit 06021020 |
| Permit Number |
06021020 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-27 00:00:00 | *** DENIED *** | | | 1) PLANS MUST SHOW NAME OF COMPANY, | | | ADDRESS, PHONE NUMBER, AND LIC. NUMBER. | | | | | | 2)ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | 3) PLEASE SHOW SIZE OF GRILLS ON PLANS. | | | | | | 4) PLEASE SHOW SIZE OF RETURN AIR | | | TRANSFER GRILLS AND OR RETURN AIR DUCTS. | | | | | | 5) PLEASE SHOW LOCATION OF AHU (CLOSET | | | OR ATTIC ?). | | | | | | 6) PLEASE SHOW LOCATION AND SIZE OF MAIN | | | RETURN AIR GRILL (AND DUCT ?). | | | | | | 7) PLEASE SHOW CONDENSATE DRAIN LINE ON | | | PLANS (AND COPPER LINE SIZES). | | | | | | 8) PLEASE EXPLAIN WHY YOU ARE USING A | | | 14" SUPPLY AIR DUCT TO THE LIVING ROOM | | | GRILL FOR A RESIDENTIAL APPLICATION, | | | WHEN IT IS NOT RECOMMENDED, IF THE ROOM | | | IS THAT LARGE TWO OR THREE SMALLER DUCT | | | WOULD BE APPROPRIATE. | | | | | | 9) PLEASE LIST A/C EQUIPMENT ON | | | MECHANICAL PLANS ALSO (NOT JUST ON | | | MANUAL 'J'). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|