2006-05-24 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE IS NO FEEDER SHOWN FROM THE
 METER TO THE PIECE OF EQUIPMENT MARKED
 "WP NEW" ON THE RISER. INDICATE ALL
 CONDUIT AND CONDUCTOR TYPES AND SIZES
 PER 215.5.
  
 2} DESIGNATE ALL SERVICE EQUIPMENT. THE
 PANEL AT THE PROPOSED SHED IS LABLED
 "A", BUT NO PANEL "A" APPEARS ON THE
 RISER DIAGRAM.
  
 3} SHOW THE LOCATION OF ALL EQUIPMENT
 INDICATED ON THE RISER, ON THE PLAN.
  
 4} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 5} 210.8(A)(2)GARAGES, AND ALSO
 ACCESSORY BUILDINGS THAT HAVE A FLOOR
 LOCATED AT OR BELOW GRADE LEVEL NOT
 INTENDED AS HABITABLE ROOMS AND LIMITED
 TO STORAGE AREAS, WORK AREAS, AND AREAS
 OF SIMILAR USE
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  