| Plan Review Notes For Permit 06021006 |
| Permit Number |
06021006 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-10-20 15:21:33 | | | | | | | NONCOMPLIANT | | | | | | THE LOAD CALCULATION AFTER DEMANDS, IS 240 AMPS. THE | | | SERVICE CONDUCTORS ARE RATED AT 230 AMPS. NOTE THIS IS | | | A QUADRAPLEX AND TABLE 310.15(B)(6) DOES NOT APPLY. | | | PLEASE | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|