| Plan Review Notes For Permit 06021006 |
| Permit Number |
06021006 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-03 00:00:00 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SUBMIT A PANEL SCHEDULE FOR ALL | | | UNITS, 106.3.5.4 FBC, AS AMMENDED. | | | | | | 2} THERE ARE WASHERS AND DRYERS ON THE | | | PLAN, NONE IN THE CALCS OR ON THE | | | SCHEDULES. | | | | | | 3} THERE ARE WATER HEATERS SHOWN OUTSIDE | | | OF UNITS 1 AND 3, BESIDES THE ONES SHOWN | | | INSIDE. | | | | | | 4} IF THE WATER HEATERS AND | | | WASHER/DRYERS ARE FOR COMMON USE OF ALL | | | APARTMENTS, A HOUSE PANEL IS REQUIED. | | | | | | 5} PROVIDE A RISER DIAGRAM PER 215.5. | | | | | | THE NEXT COMMENTS ARE FROM A PREVIOUS | | | REVIEW. THE NUMBERS REFLECT THE COMMENT | | | NUMBERS FROM THAT REVIEW. | | | | | | 5} THE PANEL SCHEDULE INDICATES ONE | | | SMALL APPLIANCE CIRCUIT AND THE CALC'S | | | INDICATE THREE. SEE 210.11(C)(1). | | | | | | 6} PLEASE LOCATE ALL SERVICE EQUIPMENT | | | ON THE PLAN, METER ENCLOSURE, | | | DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN | | | BE REVIEWED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | |
|