| Plan Review Notes For Permit 06021006 |
| Permit Number |
06021006 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-13 00:00:00 | DENIED; | | | 1.A BACKFLOW PREVENTOR IS REQUIRED ON | | | THE WATER SERVICE IF THE UNITS ARE NOT | | | INDIVIDUALLY METERED. PLEASE INDICATE ON | | | PLANS. | | | 2.LIST FIREW STOP MATERIAL TO BE USED, | | | AND LIST THE UL LISTINGS. | | | 3.THERMAL EXPANTION PROTECTION IS | | | REQUIRED ON WATER HEATER IF A BACKFLOW | | | PREVENTOR IS INSTALLED PER SEC.607.3. | | | 4.ADD NOTE "ALL NEW PIPING SHALL BE | | | TESTED PER FBC-2004 PLUMBING SEC.312.1. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|