| Plan Review Notes For Permit 06021006 |
| Permit Number |
06021006 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-09 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1}THERE ARE FLOOR PLANS ON SHEET 3/5 | | | AND SHEET 5/5. REMOVE THE ONE NO TTO BE | | | REVIEWED. PREFERABLE USE THE SCALE ON | | | SHEET 3/5. | | | | | | 2} THERE IS ONLY ONE FLOOR, TWO UNITS, | | | ON THE PLAN. PROVIDE DRAWINGS FOR ALL | | | UNITS AND INDICATE UNIT NUMBERS. | | | | | | 3} THERE IS A SMOKE DETECTOR MISSING IN | | | ONE UNIT, AND A KITCHEN GFI IN ANOTHER. | | | UNITS HAVE NO DESIGNATIION, SEE REVIEWED | | | PLAN FOR REDLINES. | | | | | | 4} THERE IS A BATH GFI MISSING . | | | | | | 5} THE PANEL SCHEDULE INDICATES ONE | | | SMALL APPLIANCE CRCUIT AND THE CALC'S | | | INDICATE THREE. SEE 210.11(C)(1). | | | | | | 6} PLEASE LOCATE ALL SERVICE EQUIPMENT | | | ON THE PLAN, METER ENCLOSURE, | | | DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN | | | BE REVIEWED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | |
|