| Plan Review Notes For Permit 06020972 |
| Permit Number |
06020972 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-01-08 18:48:57 | REVISION DENIED BY BUILDING | | | | | | 1) THE SCOPE OF THE WORK HAS BEEN INCREASED, SUCH THAT | | | IT EXCEEDS THE VALUE OF WORK DECLARED ON THE ORIGINAL | | | PERMIT APPLICATION. PLEASE PROVIDE THE COST OF THE | | | ADDITIONAL WORK , SO THAT THE PERMIT VALUE CAN BE | | | ADJUSTED APPROPRIATLY. | | | | | | 2) SPECIFY THE WIND DESIGN DATA FOR THE EXTERIOR WORK | | | ON SHEET A3.2. SEE FBC 1603.1.4. | | | | | | 3) SPECIFY THE ATTACHMENTS FOR THE METAL STUDS TO THE | | | MASNORY AND THE PLYWOOD TO THE METAL STUDS. SPECIFY | | | FASTENER TYPE, SIZE, EMBED DEPTH, SPACING, ETC. | | | | | | 4) PROVIDE PRODUCT APPROVALS FOR ROOFING MATERIALS OR | | | APPLY UNDER SEPARATE PERMIT.) WPB ADMIN CODE 106.3* | | | PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|