2006-05-17 00:00:00DENIED BY BUILDING
  
 1) SUBMIT PRODUCT APPROVALS FOR THE NEW
 EXTERIOR WINDOWS AND DOORS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE WWW.
 FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
 (IF YOU FIND THAT THE QUOTED WEB PAGE IS
 NO LONGER AVAILABLE, PLEASE INFORM THE
 PLAN REVIEWER)
  
 2) FBC 106.3.3* (CITY AMENDMENTS)
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) THE CITY OF WEST PALM BEACH IS
 LOCATED IN THE WIND-BORNE DEBRIS REGION.
 FBC 1609.1.4 REQUIRES EXTERIOR GLAZING
 TO BE IMPACT RESISTANT OR PROTECTED WITH
 IMPACT RESISTANT COVERINGS. THE USE OF
 REMOVABLE STORM PANELS OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES ON COMMERCIAL
 BUILDINGS REQUIRE THE APPROVAL OF THE
 BUILDING OFFICIAL (CALL FOR DETAILS).
  
 4) SPECIFY THE TYPE OF CONSTRUCTION OF
 THE STRUCTURE USING FBC 2004
 DESIGNATION. SEE 2004 FBC 602.
  
 5) SPECIFY THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR THE NEW EXTERIOR
 WINDOW/DOOR OPENINGS AND THE EXISTING
 OPENINGS WHERE WINDOWS/DOORS ARE BEING
 REPLACED. SEE FBC 1603.1.4(5).
  
 6) PROVIDE BUCK FASTENING DETAILS FOR
 NEW WINDOW AND DOOR OPENINGS. SEE FBC
 1714.5.4.2
  
 7) SPECIFY THE FIRE SEPARATION DISTANCE
 AND SHOW COMPLIANCE WITH ALLOWABLE AREA
 OF OPENINGS IN NORTH WALL WHERE OPENINGS
 ARE BEING ADDED AND INCREASED. SEE FBC
 704.8, 704.3 AND 702.
  
 8) FBC 1013.2 EGRESS THROUGH
 INTERVENING SPACES.
 EGRESS FROM A ROOM OR SPACE SHALL NOT
 PASS THROUGH ADJOINING OR INTERVENING
 ROOMS OR AREAS, EXCEPT WHERE SUCH
 ADJOINING ROOMS OR AREAS ARE ACCESSORY
 TO THE AREA SERVED; ARE NOT A
 HIGH-HAZARD OCCUPANCY AND PROVIDE A
 DISCERNIBLE PATH OF EGRESS TRAVEL TO AN
 EXIT. EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR
 SPACES USED FOR SIMILAR PURPOSES. AN
 EXIT ACCESS SHALL NOT PASS THROUGH A
 ROOM THAT CAN BE LOCKED TO PREVENT
 EGRESS. MEANS OF EGRESS FROM DWELLING
 UNITS OR SLEEPING AREAS SHALL NOT LEAD
 THROUGH OTHER SLEEPING AREAS, TOILET
 ROOMS OR BATHROOMS. THIS SECTION DOES
 NOT ALLOW EGRESS THROUGH A KITCHEN IN A
 BUSINESS OCCUPANCY. IF THIS IS A
 BREAKROOM WITH NO STOVE OR OVEN THEN
 EGRESS THROUGH IT WILL BE PERMITTED.
 CHANGE ROOM DESIGNATION ON THE PLAN.
  
 9) 1005.2 DOOR ENCROACHMENT.
 DOORS OPENING INTO THE PATH OF EGRESS
 TRAVEL SHALL NOT REDUCE THE REQUIRED
 WIDTH TO LESS THAN ONE-HALF DURING THE
 COURSE OF THE SWING. WHEN FULLY OPEN,
 THE DOOR SHALL NOT PROJECT MORE THAN 7
 INCHES (178 MM) INTO THE REQUIRED WIDTH.
 SEE DOOR TO ACCESSIBLE TOLIET ROOM. THE
 REQUIRED EGRESS WIDTH IS 36" AND THE
 SWING OF THE ACCESSIBLE TOLIET ROOM DOOR
 REDUCES THE EGRESS PATH OF TRAVHIS IEL
 BY MORE THAN ONE-HALF. PLEASE CORRECT.
  
  
 10) FBC 11-7.2 SALES AND SERVICE
 COUNTERS, TELLER WINDOWS, INFORMATION
 COUNTERS.
 (2)AT TICKETING COUNTERS, TELLER
 STATIONS IN A BANK, REGISTRATION
 COUNTERS IN HOTELS AND MOTELS, BOX
 OFFICE TICKET COUNTERS, AND OTHER
 COUNTERS THAT MAY NOT HAVE A CASH
 REGISTER BUT AT WHICH GOODS OR SERVICES
 ARE SOLD OR DISTRIBUTED, EITHER:
 (I)A PORTION OF THE MAIN COUNTER
 WHICH IS A MINIMUM OF 36 INCHES (915 MM)
 IN LENGTH SHALL BE PROVIDED WITH A
 MAXIMUM HEIGHT OF 36 INCHES (915 MM); OR
  
 (II)AN AUXILIARY COUNTER WITH A
 MAXIMUM HEIGHT OF 36 IN (915 MM) IN
 CLOSE PROXIMITY TO THE MAIN COUNTER
 SHALL BE PROVIDED; OR
 (III)EQUIVALENT FACILITATION SHALL
 BE PROVIDED (E.G., AT A HOTEL
 REGISTRATION COUNTER, EQUIVALENT
 FACILITATION MIGHT CONSIST OF:
 (1)PROVISION OF A FOLDING SHELF
 ATTACHED TO THE MAIN COUNTER ON WHICH AN
 INDIVIDUAL WITH DISABILITIES CAN WRITE,
 AND
 (2)USE OF THE SPACE ON THE SIDE OF
 THE COUNTER OR AT THE CONCIERGE DESK,
 FOR HANDING MATERIALS BACK AND FORTH).
 ALL ACCESSIBLE SALES AND SERVICE
 COUNTERS SHALL BE ON AN ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 .
 REVISE RECEPTION DESK TO COMPLY.
  
 11) PLEASE REMOVE ALL OLD SHEETS THAT
 HAVE BEEN REVISED FROM THE PLANS AND
 INSERT THE NEW SHEETS SO THAT TWO
 COMPLETE SETS OF PLANS ARE CREATED. TWO
 COMPLETE SETS OF PLANS ARE REQUIRED TO
 BE SUBMITTED FOR PERMIT.
  
 NOTE: ITEMS 1-10 WERE REQUESTED IN THE
 PREVIOUS REVIEW BUT HAVE NOT BEEN
 ADDRESSED. A RESPONSE LETTER STATING HOW
 THE COMMENTS WERE ADDRESSED WILL BE
 HELPFUL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714