2006-04-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE REFERENCE TO ARTICLE
 250.30(A)(4)IN THE RISER DIAGRAM, DOES
 NOT APPLY. THIS METER AND DISCONNECT ARE
 NOT A SEPERATE SYSTEM AS THEY ARE FED
 FROM THE SAME TRANSFORMER AS THE REST OF
 THE SERVICE EQUIPMENT.
 THIS SERVICE SHOULD BE GROUNDED AT A
 COMMON LOCATION . PLEASE INDICATE GEC
 SYSTEM (EXISTING) ON THE RISER. ADDING
 THE GROUNDING POINT INDICATED WILL
 PROBABLY CREATE A PARALLEL GROUND PATH
 IN VIOLATION OF 250.6.
  
 2} THE REFERENCE IN THE ELECTRICAL NOTE
 #1 IS INCORRECT. 2004 FBC, 2002 NEC IS
 CURRENT.
  
 3} BRANCH-CIRCUIT CONDUCTORS SHALL HAVE
 AN AMPACITY NOT LESS THAN THE MAXIMUM
 LOAD TO BE SERVED. WHERE A BRANCH
 CIRCUIT SUPPLIES CONTINUOUS LOADS OR ANY
 COMBINATION OF CONTINUOUS AND
 NONCONTINUOUS LOADS, THE MINIMUM
 BRANCH-CIRCUIT CONDUCTOR SIZE, BEFORE
 THE APPLICATION OF ANY ADJUSTMENT OR
 CORRECTION FACTORS, SHALL HAVE AN
 ALLOWABLE AMPACITY NOT LESS THAN THE
 NONCONTINUOUS LOAD PLUS 125 PERCENT OF
 THE CONTINUOUS LOAD. 210.19(A)(1),
 INCLUDE IN LOAD CALCULATIONS.
  
 4} SHOW COMPLIANCE OF THE ENERGY CODE
 DIAGRAMMATICALLY IF APPLICABLE. SEE
 CHAPTER 13 FBC.(500 SQ FT.).
  