| 2006-04-14 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE REFERENCE TO ARTICLE |
| | 250.30(A)(4)IN THE RISER DIAGRAM, DOES |
| | NOT APPLY. THIS METER AND DISCONNECT ARE |
| | NOT A SEPERATE SYSTEM AS THEY ARE FED |
| | FROM THE SAME TRANSFORMER AS THE REST OF |
| | THE SERVICE EQUIPMENT. |
| | THIS SERVICE SHOULD BE GROUNDED AT A |
| | COMMON LOCATION . PLEASE INDICATE GEC |
| | SYSTEM (EXISTING) ON THE RISER. ADDING |
| | THE GROUNDING POINT INDICATED WILL |
| | PROBABLY CREATE A PARALLEL GROUND PATH |
| | IN VIOLATION OF 250.6. |
| | |
| | 2} THE REFERENCE IN THE ELECTRICAL NOTE |
| | #1 IS INCORRECT. 2004 FBC, 2002 NEC IS |
| | CURRENT. |
| | |
| | 3} BRANCH-CIRCUIT CONDUCTORS SHALL HAVE |
| | AN AMPACITY NOT LESS THAN THE MAXIMUM |
| | LOAD TO BE SERVED. WHERE A BRANCH |
| | CIRCUIT SUPPLIES CONTINUOUS LOADS OR ANY |
| | COMBINATION OF CONTINUOUS AND |
| | NONCONTINUOUS LOADS, THE MINIMUM |
| | BRANCH-CIRCUIT CONDUCTOR SIZE, BEFORE |
| | THE APPLICATION OF ANY ADJUSTMENT OR |
| | CORRECTION FACTORS, SHALL HAVE AN |
| | ALLOWABLE AMPACITY NOT LESS THAN THE |
| | NONCONTINUOUS LOAD PLUS 125 PERCENT OF |
| | THE CONTINUOUS LOAD. 210.19(A)(1), |
| | INCLUDE IN LOAD CALCULATIONS. |
| | |
| | 4} SHOW COMPLIANCE OF THE ENERGY CODE |
| | DIAGRAMMATICALLY IF APPLICABLE. SEE |
| | CHAPTER 13 FBC.(500 SQ FT.). |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |
| | |
| | |
| | |
| | |