Plan Review Notes
Plan Review Notes For Permit 06020972
Permit Number 06020972
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-14 00:00:00DENIED
  
 1) THE REQUIRED EXITS FOR THE ADJACENT
 OCCUPANCY MUST BE MAINTAINED DURING
 DEMOLITION AND CONSTRUCTION.
  
 2)PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT TWO COPIES OF STATE PRODUCT
 APPROVALS FOR THE NEW EXTERIOR WINDOW.
  
 3) THE PRINTED NAME OF THE ARCHITECT
 SIGNING AND SEALING THE DRAWINGS IS
 REQUIRED. SEE FAC 61G-16.004.
  
 4) MANEUVERING CLEARANCES AT DOORS
 MINIMUM OF 18" ON PULL SIDE OF DOORS
 REQUIRED BY 11-4.13.6. INDICATE THIS AT
 DOOR #2. CLARIFY DOOR SCHEDULE NOTE 2 ON
 A3.0.
  
 5) SHOW LOCATIONS OF EXIT LIGHTS. SEE
 FBC 1006.3.
  
 6) SPECIFY THE WALL AND CEILING FINISH
 CLASSES THAT ARE ALLOWED BY CODE. SEE
 FBC 803.
  
 7) PROVIDE A LIFE SAFETY PLAN SHOWING
 THE COMMON PATHS OF TRAVEL, ETC. TO THE
 EXITS. SEE FBC CHAPTER 10 MEANS OF
 EGRESS.
  
 8) REVISE NOTES ON SHEET A1.0 TO COMPLY
 WITH 2004 FBC. SECTIONS HAVE CHANGED.
  
 9) REVISE CONSTRUCTION TYPE TO CONCUR
 WITH 2004 FBC. TYPE IV UNPROTECTED
 EQUATES TO TYPE II B. SEE FBC CHAPTER 3.
  
 10) THE NOTE ON A1.0 STATES THAT NO FIRE
 SPRINKLER SYSTEM IS REQUIRED. SPECIFY IF
 THE STRUCTURE IS SPRINKLERED OR
 UNSPRINKLERED. THE NOTES GIVE TRAVEL
 DISTANCES, DEAD ENDS, BUILDING AREA,
 ETC. BASED ON A FULLY SPRINKLERED
 BUILDING.
  
 11) COMMON PATH OF TRAVEL IS NOT TO
 EXCEED 75' IF BUILDING IS NOT
 SPRINKLERED PER FBC 1013.3.
  
 12) TRAVEL DISTANCE FOR UNSPRINKLERED
 BUILD IS 200' AND DEAD END CORRIDOR
 LENGTH IS 20'.
  
 13) THE EGRESS CAPACITY CALCUATION ON
 A1.0 HAS 19 PERSONS WHERE IT SHOULD HAVE
 BEEN 24. PLEASE CORRECT. SEE NOTATIONS
 ON PLAN.
  
 14) THE OCCUPANCY AREA MODIFICATION NOTE
 ON A1.0 IS INCOMPLETE. IN ADDITION TO
 FIRE SPRINKLERS THE ONE STORY BUILDING
 WITH A BUSINESS OCCUPANCY IS REQUIRED TO
 BE SURROUNDED AND ADJOINED BY PUBLIC
 WAYS OR YARDS NOT LESS THAN 60' IN WIDTH
 IN ORDER TO HAVE UNLIMITED AREA PER FBC
 507.2
  
 15) A TENANT SEPARATION WALL WITH A ONE
 HOUR FIRE-RESISTANCE RATING IS REQUIRED
 BETWEEN THIS SPACE AND THE ADJACENT
 TENANT. SEE FBC 708.1 AND 708.3.
  
 16) CORRECT WINDLOAD INFORMATION ON
 SHEET A1.0. THE WINDSPEED FOR WEST PALM
 BEACH IS 140 MPH. THE WINDSPEED MAP IN
 THE 2004 FBC IS FIGURE 1609.
  
 17)11-4.1.6(2) DUTY TO PROVIDE
 AN ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 SUBMIT A COST BREAKDOWN SHOWING THAT 20%
 OF THE CONSTRUCTION COST HAS BEEN SPENT
 ON ACCESSIBILITY.
  
 18)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  