Notes
Date Text
2007-04-13 11:15:45 
  
  
 DENIED
  
 AS PER NOTE #4- 3/9/06, NOTE #2 -6/2106, AS A NOTE ON
 10/23/06 AND FINALLY AS A PROVISO PENDING FLOOR PLAN
 DESIGNATION CORRECTION ON 1/10/07 ZONING HAS
 CONTINUALLY NOTED THAT ONLY ONE KITCHEN WAS ALLOWED IN
 THE GUEST UNIT. THE LOWER UNIT ON SHEET E-3 HAS NEVER
 BEEN CHANGED TO CORRELATE WITH SHEET A-2.
  
 NOTE #4-6/24/06, NOTE#3-10/27/06 AND A COMMENT THAT THE
 COMMENTS FROM PREVIOUS REVIEWS WERE NOT ADDRESSED ON
 3/19/07, ON THE ELECTRICAL REVIEWS INDICATED THE SAME
 DISCREPANCY, BUT SHEET E-3 SHOWING THE KITCHEN WAS
 RESUBMITTED FOR THE FOURTH TIME ON 4/6/07.
  
 DO NOT RESUBMIT SHEET E-3 WITH A KITCHEN ON THE 1ST
 FLOOR OF THE GUEST HOUSE. REMOVE THE FULL SIZE
 REFRIGERATOR, REMOVE THE SMALL APPLIANCE CIRCUITS AND
 CORRECT THE LOAD CALCULATIONS AFFECTED BY THIS CHANGE.
  
  
 CONTACT THE ARCHITECT TO CONFIRM ROOM DESIGNATIONS AND
 LAYOUT IF NECESSARY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718