 THERE HAVE BEEN NO ELECTRICAL SHEET CHANGES SINCE THE
 LAST REVIEW. SEE DATES ON SHEETS. THERE ARE SEVERAL
 SETS FROM PREVIOUS REVIEWS RESUBMITTED. REMOVE ALL OLD
 SHEETS FROM THE PLANS, INSERT NEW CODE COMPLIANT
 SHEETS. 10/27/06.
  
 ADDRESS ALL NOTES FROM PREVIOUS REVIEWS. PLEASE NOTE
 THAT 250.24 AND 250.6.} THE EQUIPMENT GROUND BETWEEN
 THE METER AND DISCONNECT ON THE RISER DIAGRAM CREATES A
 PARALLEL PATH TO GROUND WITH THE NEUTRAL AND MUST BE
 REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE
 TO BE RAN FROM THE FIRST MEANS OF DISCONNECT.
  