 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
 1} 250.64 GROUNDING ELECTRODE CONDUCTOR
 INSTALLATION.(C) CONTINUOUS. THE GROUNDING ELECTRODE
 CONDUCTOR SHALL BE INSTALLED IN ONE CONTINUOUS LENGTH
 WITHOUT A SPLICE OR JOINT, UNLESS SPLICED ONLY BY
 IRREVERSIBLE COMPRESSION-TYPE CONNECTORS LISTED FOR THE
 PURPOSE OR BY THE EXOTHERMIC WELDING PROCESS.
  
 2} THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR OF A
 GROUNDED OR UNGROUNDED AC SYSTEM SHALL NOT BE LESS THAN
 GIVEN IN TABLE 250.66.( 1/0 MINIMUM FOR 400 MCM COPPER
 CONDUCTORS.)
  
 3} THE ROOM DESIGNATIONS ON THE ELECTRICAL PLAN FOR THE
 GUEST HOUSE ARE NOT THE SAME AS ON THE ARCHITECTURALS.
 SEE A2 AND E3, ALSO SEE ZONING NOTES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.