| 2006-06-24 00:00:00 | ****** UNSAT ******** |
| | |
| | 1) NOTE: PLEASE BE SURE TO COMPLETELY |
| | REMOVED ANY OF THE OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT THE NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | THIS WILL HELP TO AVOID ANY DELAYS IN |
| | PROCESSING PROJECT. |
| | ** ONE COPY OF ANY OLD/VOIDED REMOVED |
| | SHEETS SHOULD BE SUBMITTED SEPARATELY |
| | FOR REFERENCE. |
| | |
| | 2) NOTE: PLEASE SEE FIRM ON "S" SHEETS |
| | WHICH IS MISSING THE REQUIRED |
| | CERTIFICATE OF AUTHORIZATION # AS |
| | REQUIRED PER FAC 61G15-23.002, FS |
| | 471.023 |
| | THIS IS ONLY NOTED, HOWEVER IS REQUIRED |
| | EVEN IFCOMMENT IS NOT MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE PLANS SHALL |
| | REFERENCE THE CURRENT CODES IN EFFECT. |
| | PLEASE SEE PLANS NOW INDICATE THE |
| | "LATEST CODES". WE ARE NOT CURRENTLY |
| | UNDER THE LATEST CODES AS THEY HAVE NOT |
| | YET BEEN ADOPTED BY THE STATE OF |
| | FLORIDA. |
| | PLEASE SEE THE FOLLOWING AT A MIN SHOULD |
| | BEON PLANS. 2002 NFPA-70, 2003 NFPA-101, |
| | 2002 NFPA-72. |
| | |
| | 4) NOTE: PLEASE SEE ZONING COMMENTS AS |
| | THESE WILL HAVE A DIRECT AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | 5) NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING CONTROLS IN MANY LOCATIONS. |
| | PLEASE SEE CONTROL REQUIRED AT FIRST FLR |
| | AT CABANA LEADING TO 2ND FLR FOR STAIR |
| | LTS. PLEASE SEE MISSING 1ST AND 2ND FLR |
| | CONTROL AT SPIRAL STAIRS SHOWN AT MAIN |
| | HOUSE. |
| | PLEASE SEE MISSING CONTROL EXISTING FROM |
| | BEDRM #2 INTO HALL AS THE 3-WAY IS DOWN |
| | THE HALL. |
| | PLEASE SEE ALL RMS AT GUEST HOUSE AND |
| | APT WHICH INDICATE A SW FOR A FAN AND A |
| | FAN J-BOX ONLY?? |
| | PLEASE KNOW, A LT FIXTURE WILL BE |
| | REQUIRED OR 1/2 SWITCHED RECEPT. |
| | PLEASE SEE OTHER LOCATIONS IN MAIN HOUSE |
| | ALSO BUT MAINLY CABANA HOUSE. |
| | 210.70, LS 101 7.8, RESIDENTIAL CHAPTER |
| | 24. |
| | |
| | 6) NOTE: PLEASE SEE SD'S ARE NOT SHOWN |
| | WITH CIRCUITING , HOWEVER PANEL |
| | SCHEDULES ARE SHOWING THESE ON A |
| | DEDICATED CIRCUIT. PLEASE KNOW, THE SD'S |
| | IN EACH DWELLING CAN BE CIRCUITED TO ONE |
| | OF THE ARC FAULT PROTECTED BEDRM |
| | LIGHTING/RECEPT CIRCUITS. THIS WILL |
| | ALLEAVIATE THE TURNING OFF OF THIS |
| | CIRCUIT AND LEAVING THE ENTIRE DWELLING |
| | WITH OUT SD PROTECTION. ( THIS WOULD |
| | ALSO ALLEAVIATE THE ADDITIONAL AFCI |
| | BRKR) |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE CABANA SEEMS TO SHOW |
| | DOORS IN FRONT OF RANGE? PLEASE VERIFY |
| | COMBUSTIBLES AND LOCATION AS SHOWN. |
| | THIS IS ONLY NOTED. |
| | |
| | 8) NOTE: PLEASE SEE DRYER IN CAB SHOWS |
| | 50A BRKR FOR 30A DRYER?? PLEASE SEE MAX |
| | OCPFOR 30A RECEPT. |
| | PLEASE ALSO SEE DRYER IN MAIN HOUSE |
| | WHICH INDICATES 50A OCP ON 30A RECEPT. |
| | PLEASE SEE 210.21 WHERE THIS IS NOT |
| | PERMITTED. |
| | |
| | 9) NOTE: PLEASE SEE MIN VA TO BE FIGURED |
| | FOR DRYER. 5KW 220.18 |
| | |
| | 10) NOTE: PLEASE SEE 210.52, 210.11C1, |
| | 220.16 FOR MIN OF 1.5KW TO BE FIGUURED |
| | FOR WASHER/LAUNDRY CIRCUIT.(SHOWS .9)FOR |
| | BOTH DWELLINGS. |
| | |
| | 11) NOTE: PLEASE SEE CABANA, MAX OCP FOR |
| | WH IS 150%, HOWEVER OCP EXCEEDS THIS , |
| | AS THE 3.5 KW UNIT SHOWS 2-POLE 30A |
| | BRKR. (MAX 25A). |
| | 422.11 |
| | |
| | 12) NOTE: PLEASE SEE 408.4 WHERE THE |
| | PANEL SCHEDULE SHALL BE SPECIFIC FOR |
| | ROOMS AND ALL AREAS. PLEASE ALSO |
| | IDENTIFY THE "BATH GFI" CIRCUITS. |
| | IE: BEDRM #3 RECEPTS , LIV RM LTS ETC |
| | ** IT IS KNOWN, THAT DURING CONSTRUCTION |
| | THESE CIRCUITS MAY CHANGE AND CAN BE |
| | REVISED AT A LATER DATE. |
| | |
| | 13) NOTE: PLEASE SEE MISSING RECEPT PER |
| | 210.52 IN BEDRM #2 (MAIN HOUSE) |
| | |
| | 14) NOTE: PLEASE SEE MISSSING HALLWAY |
| | RECEPT PER 210.52H CAB 2ND FLR) |
| | |
| | 15) NOTE: PLEASE SPECIFY SIZE OF |
| | METERBANK AS A 325A SERVICE IS BEING |
| | PROVIDED. |
| | PLEASE SEE MIN SIZE OF THE SEC'S SHALL |
| | BE 350 MCM BASED ON 310.15B6. |
| | PLEASE SEE THE RISER SIZE WILL ALSO |
| | CHANGE PER TABLES (9). |
| | PLEASE SEE 240.4, 310.15B6,215.5 |
| | |
| | 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 17) NOTE: PLEASE SEE RISER IS SHOWING |
| | "EQUIPMENT GROUNDING CONDUCTORS" FROM |
| | METER TO MAINS. PLEASE SEE THE EQP GRNDS |
| | ARE ONLY INSTALLED AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | 250.6,250.24B |
| | |
| | 18) NOTE: PLEASE SEE 410.8 FOR MIN |
| | CLEARENCES REQUIRED FOR CLOSET LTS. |
| | PLEASE SEE GUEST HOUSE AS THESE ARE |
| | RIGHT NEXT TO SHELVES WHICH ARE NOT |
| | PERMITTED. |
| | |
| | 19) NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | RISER SHALL INCLUDE ANY NEW FOOTER STEEL |
| | AS REQUIRED PER 250.50. |
| | |
| | 20) NOTE: PLEASE SEE DISCONNECT AND AHU |
| | IN UPSTAIRS CLOSET SEEMS TO BE LOCATED |
| | NOT TO MEET 110.26. PLEASE ALSO SEE |
| | 240.24D AS OCP IS NOT PERMITTED IN A |
| | CLOTHES CLOSET. |
| | |
| | 21) NOTE: PLEASE SEE THIS WOULD ALSO |
| | INCLUDE ANY CLOSET WHERE OCP FOR WATER |
| | HEATERS ARE LOCATED. |
| | PLEASE ALSO SEE MIN SEPARATIONS REQUIRED |
| | PER 422.17 |
| | |
| | ** PLEASE SUBMIT THE ABOVE FOR REVIEW |
| | AND IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |