Plan Review Notes
Plan Review Notes For Permit 06020956
Permit Number 06020956
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-24 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE BE SURE TO COMPLETELY
 REMOVED ANY OF THE OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT THE NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 THIS WILL HELP TO AVOID ANY DELAYS IN
 PROCESSING PROJECT.
 ** ONE COPY OF ANY OLD/VOIDED REMOVED
 SHEETS SHOULD BE SUBMITTED SEPARATELY
 FOR REFERENCE.
  
 2) NOTE: PLEASE SEE FIRM ON "S" SHEETS
 WHICH IS MISSING THE REQUIRED
 CERTIFICATE OF AUTHORIZATION # AS
 REQUIRED PER FAC 61G15-23.002, FS
 471.023
 THIS IS ONLY NOTED, HOWEVER IS REQUIRED
 EVEN IFCOMMENT IS NOT MADE BY OTHER
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE PLANS SHALL
 REFERENCE THE CURRENT CODES IN EFFECT.
 PLEASE SEE PLANS NOW INDICATE THE
 "LATEST CODES". WE ARE NOT CURRENTLY
 UNDER THE LATEST CODES AS THEY HAVE NOT
 YET BEEN ADOPTED BY THE STATE OF
 FLORIDA.
 PLEASE SEE THE FOLLOWING AT A MIN SHOULD
 BEON PLANS. 2002 NFPA-70, 2003 NFPA-101,
 2002 NFPA-72.
  
 4) NOTE: PLEASE SEE ZONING COMMENTS AS
 THESE WILL HAVE A DIRECT AFFECT ON
 ELECTRICAL PLANS.
  
 5) NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROLS IN MANY LOCATIONS.
 PLEASE SEE CONTROL REQUIRED AT FIRST FLR
 AT CABANA LEADING TO 2ND FLR FOR STAIR
 LTS. PLEASE SEE MISSING 1ST AND 2ND FLR
 CONTROL AT SPIRAL STAIRS SHOWN AT MAIN
 HOUSE.
 PLEASE SEE MISSING CONTROL EXISTING FROM
 BEDRM #2 INTO HALL AS THE 3-WAY IS DOWN
 THE HALL.
 PLEASE SEE ALL RMS AT GUEST HOUSE AND
 APT WHICH INDICATE A SW FOR A FAN AND A
 FAN J-BOX ONLY??
 PLEASE KNOW, A LT FIXTURE WILL BE
 REQUIRED OR 1/2 SWITCHED RECEPT.
 PLEASE SEE OTHER LOCATIONS IN MAIN HOUSE
 ALSO BUT MAINLY CABANA HOUSE.
 210.70, LS 101 7.8, RESIDENTIAL CHAPTER
 24.
  
 6) NOTE: PLEASE SEE SD'S ARE NOT SHOWN
 WITH CIRCUITING , HOWEVER PANEL
 SCHEDULES ARE SHOWING THESE ON A
 DEDICATED CIRCUIT. PLEASE KNOW, THE SD'S
 IN EACH DWELLING CAN BE CIRCUITED TO ONE
 OF THE ARC FAULT PROTECTED BEDRM
 LIGHTING/RECEPT CIRCUITS. THIS WILL
 ALLEAVIATE THE TURNING OFF OF THIS
 CIRCUIT AND LEAVING THE ENTIRE DWELLING
 WITH OUT SD PROTECTION. ( THIS WOULD
 ALSO ALLEAVIATE THE ADDITIONAL AFCI
 BRKR)
 215.5
  
 7) NOTE: PLEASE SEE CABANA SEEMS TO SHOW
 DOORS IN FRONT OF RANGE? PLEASE VERIFY
 COMBUSTIBLES AND LOCATION AS SHOWN.
 THIS IS ONLY NOTED.
  
 8) NOTE: PLEASE SEE DRYER IN CAB SHOWS
 50A BRKR FOR 30A DRYER?? PLEASE SEE MAX
 OCPFOR 30A RECEPT.
 PLEASE ALSO SEE DRYER IN MAIN HOUSE
 WHICH INDICATES 50A OCP ON 30A RECEPT.
 PLEASE SEE 210.21 WHERE THIS IS NOT
 PERMITTED.
  
 9) NOTE: PLEASE SEE MIN VA TO BE FIGURED
 FOR DRYER. 5KW 220.18
  
 10) NOTE: PLEASE SEE 210.52, 210.11C1,
 220.16 FOR MIN OF 1.5KW TO BE FIGUURED
 FOR WASHER/LAUNDRY CIRCUIT.(SHOWS .9)FOR
 BOTH DWELLINGS.
  
 11) NOTE: PLEASE SEE CABANA, MAX OCP FOR
 WH IS 150%, HOWEVER OCP EXCEEDS THIS ,
 AS THE 3.5 KW UNIT SHOWS 2-POLE 30A
 BRKR. (MAX 25A).
 422.11
  
 12) NOTE: PLEASE SEE 408.4 WHERE THE
 PANEL SCHEDULE SHALL BE SPECIFIC FOR
 ROOMS AND ALL AREAS. PLEASE ALSO
 IDENTIFY THE "BATH GFI" CIRCUITS.
 IE: BEDRM #3 RECEPTS , LIV RM LTS ETC
 ** IT IS KNOWN, THAT DURING CONSTRUCTION
 THESE CIRCUITS MAY CHANGE AND CAN BE
 REVISED AT A LATER DATE.
  
 13) NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 IN BEDRM #2 (MAIN HOUSE)
  
 14) NOTE: PLEASE SEE MISSSING HALLWAY
 RECEPT PER 210.52H CAB 2ND FLR)
  
 15) NOTE: PLEASE SPECIFY SIZE OF
 METERBANK AS A 325A SERVICE IS BEING
 PROVIDED.
 PLEASE SEE MIN SIZE OF THE SEC'S SHALL
 BE 350 MCM BASED ON 310.15B6.
 PLEASE SEE THE RISER SIZE WILL ALSO
 CHANGE PER TABLES (9).
 PLEASE SEE 240.4, 310.15B6,215.5
  
 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 17) NOTE: PLEASE SEE RISER IS SHOWING
 "EQUIPMENT GROUNDING CONDUCTORS" FROM
 METER TO MAINS. PLEASE SEE THE EQP GRNDS
 ARE ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
 250.6,250.24B
  
 18) NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCES REQUIRED FOR CLOSET LTS.
 PLEASE SEE GUEST HOUSE AS THESE ARE
 RIGHT NEXT TO SHELVES WHICH ARE NOT
 PERMITTED.
  
 19) NOTE: PLEASE SEE GROUNDING ELECTRODE
 RISER SHALL INCLUDE ANY NEW FOOTER STEEL
 AS REQUIRED PER 250.50.
  
 20) NOTE: PLEASE SEE DISCONNECT AND AHU
 IN UPSTAIRS CLOSET SEEMS TO BE LOCATED
 NOT TO MEET 110.26. PLEASE ALSO SEE
 240.24D AS OCP IS NOT PERMITTED IN A
 CLOTHES CLOSET.
  
 21) NOTE: PLEASE SEE THIS WOULD ALSO
 INCLUDE ANY CLOSET WHERE OCP FOR WATER
 HEATERS ARE LOCATED.
 PLEASE ALSO SEE MIN SEPARATIONS REQUIRED
 PER 422.17
  
 ** PLEASE SUBMIT THE ABOVE FOR REVIEW
 AND IF THERE ARE ANY QUESTIONS OR
 COMMENTS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  