2006-03-27 00:00:00DENIED;
 1.PLANS REVIEWED UNDER THE FBC-2004
 CODE.
 2.WATER HAMMER ARRESTORS REQUIRED FOR
 ICEMAKER LINE AND HOT WATER (KITCHEN)
 3.WATER ISOMETRIC FIRST FLOOR BATHROOM,
 NO WATER TO TOILET.
 4.BACK HOUSE IS NOT SHOWN ON SANITARY OR
 WATER ISOMETRICS. PLEASE SHOW HOW WATER
 IS DISTRIBUTED TO THE BACK HOUSE. IF
 BOTH BUILDINGS ARE ON ONE METER A
 BACKFLOW IS REQUIRED . (UTILITY ORD.).
 ALSO A MEANS OF THERMAL EXPANSION IS
 REQUIRED PER FBC-2004 PLUMBING SEC.
 607.3. PLESE SHOW TIE-IN TO BUILDING
 SEWER.