Plan Review Notes
Plan Review Notes For Permit 06020956
Permit Number 06020956
Review Stop M
Sequence Number 1
Notes
Date Text
2006-03-23 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A . AND
 ALSO SIGNED BY OWNER/AGENT.
  
 2) PLEASE SHOW ON A/C EQUIPMENT LIST ALL
 NEW AND EXISTING A/C SYSTEMS, AND
 DESIGNATE IF NEW OR EXISTING AND ALL
 PERTINENT INFORMATION.
  
 3) NEED TO SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR FIRE PLACE IN FAMILY
 ROOM.
  
 4) PLEASE EXPLAIN WHY THE GAS LINE IS
 RUNNING UP TO THE SECOND FLOOR.
  
 5) THE RETURN AIR GRILL TO THE MASTER
 BEDROOM IS TO SMALL, PLEASE CORRECT. SEE
 NOTE #6 (C) EXCEPT.
  
 6)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.