| 2006-03-23 00:00:00 | *** DENIED *** |
| | 1)ENERGY CALCULATIONS NEED TO BE ON FORM |
| | 600A-04 (2004) PER FBC 13-600.3.A . AND |
| | ALSO SIGNED BY OWNER/AGENT. |
| | |
| | 2) PLEASE SHOW ON A/C EQUIPMENT LIST ALL |
| | NEW AND EXISTING A/C SYSTEMS, AND |
| | DESIGNATE IF NEW OR EXISTING AND ALL |
| | PERTINENT INFORMATION. |
| | |
| | 3) NEED TO SUBMIT DETAILED MANUFACTURE'S |
| | SPECIFICATION'S AND INSTALLATION |
| | INSTRUCTIONS FOR FIRE PLACE IN FAMILY |
| | ROOM. |
| | |
| | 4) PLEASE EXPLAIN WHY THE GAS LINE IS |
| | RUNNING UP TO THE SECOND FLOOR. |
| | |
| | 5) THE RETURN AIR GRILL TO THE MASTER |
| | BEDROOM IS TO SMALL, PLEASE CORRECT. SEE |
| | NOTE #6 (C) EXCEPT. |
| | |
| | 6)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |