2006-03-23 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 250.52(A)(3) CONCRETE-ENCASED
 ELECTRODE. AN ELECTRODE ENCASED BY AT
 LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED
 WITHIN AND NEAR THE BOTTOM OF A CONCRETE
 FOUNDATION OR FOOTING THAT IS IN DIRECT
 CONTACT WITH THE EARTH, CONSISTING OF AT
 LEAST 6.0 M (20 FT) OF ONE OR MORE BARE
 OR ZINC GALVANIZED OR OTHER ELECTRICALLY
 CONDUCTIVE COATED STEEL REINFORCING BARS
 OR RODS OF NOT LESS THAN 13 MM (? IN.)
 IN DIAMETER, OR CONSISTING OF AT LEAST
 6.0 M (20 FT) OF BARE COPPER CONDUCTOR
 NOT SMALLER THAN 4 AWG. REINFORCING BARS
 SHALL BE PERMITTED TO BE BONDED TOGETHER
 BY THE USUAL STEEL TIE WIRES OR OTHER
 EFFECTIVE MEANS. INDICATE ON RISER.
  
 2)(A) GROUNDING ELECTRODE. WHERE TWO OR
 MORE BUILDINGS OR STRUCTURES ARE
 SUPPLIED FROM A COMMON AC SERVICE BY A
 FEEDER(S) OR BRANCH CIRCUIT(S), THE
 GROUNDING ELECTRODE(S) REQUIRED IN PART
 III OF THIS ARTICLE AT EACH BUILDING OR
 STRUCTURE SHALL BE CONNECTED IN THE
 MANNER SPECIFIED IN 250.32(B) OR (C).
 WHERE THERE ARE NO EXISTING GROUNDING
 ELECTRODES, THE GROUNDING ELECTRODE(S)
 REQUIRED IN PART III OF THIS ARTICLE
 SHALL BE INSTALLED. SHOW ON RISER.
  
 3} THE FEED FROM PANEL A TO PANEL B IS 3
 #2'S ON THE RISER AND 2 #6'S ON PANEL
 SCHEDULE "A", CIRCUITS 11,13.
  
 4} THE BATH GFI (RM 107), IS ON CIRCUIT
 "A 16", WHICH IS SHARED BY OUTSIDE
 RECEPTACLES INVIOLATION OF
 210.11(C)(3)-BATH CIRCUITS.
  
 5} THE RECEPTACLE IN THE KITCHEN ON
 CIRCUIT "A28" SHOULD BE ON A SMALL
 APPLIANCE CIRCUIT PER 210.52(B)(1).
  
 6} BEDROOM #2 NEEDS 2 ADDED RECEPTACLES
 TO COMPLY WITH 210.52(A)(2). SEE
 REVIEWED SET.
  
 7} THE JACUZZI MUST BE GFI PROTECTED PER
 680.44.
  
 REGARDING THE APARTMENTS IN THE SEPARATE
 STRUCTURE: SHEET"E-3".
  
 1} THE SMOKE DETECTORS MUST BE ON ARC
 FAULT PROTECTED. ALSO NOTE THAT THE
 FIRST FLOOR DETECTORS ARE ON THE SECOND
 FLOOR PANEL.
  
 2} THE UPPER BATH CIRCUIT MUST COMPLY
 WITH 210.11(C)(3). SEE CIRCUIT # D-18
 FEEDS THE SMOKE DETECTORS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW