| 2006-03-23 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} 250.52(A)(3) CONCRETE-ENCASED |
| | ELECTRODE. AN ELECTRODE ENCASED BY AT |
| | LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED |
| | WITHIN AND NEAR THE BOTTOM OF A CONCRETE |
| | FOUNDATION OR FOOTING THAT IS IN DIRECT |
| | CONTACT WITH THE EARTH, CONSISTING OF AT |
| | LEAST 6.0 M (20 FT) OF ONE OR MORE BARE |
| | OR ZINC GALVANIZED OR OTHER ELECTRICALLY |
| | CONDUCTIVE COATED STEEL REINFORCING BARS |
| | OR RODS OF NOT LESS THAN 13 MM (? IN.) |
| | IN DIAMETER, OR CONSISTING OF AT LEAST |
| | 6.0 M (20 FT) OF BARE COPPER CONDUCTOR |
| | NOT SMALLER THAN 4 AWG. REINFORCING BARS |
| | SHALL BE PERMITTED TO BE BONDED TOGETHER |
| | BY THE USUAL STEEL TIE WIRES OR OTHER |
| | EFFECTIVE MEANS. INDICATE ON RISER. |
| | |
| | 2)(A) GROUNDING ELECTRODE. WHERE TWO OR |
| | MORE BUILDINGS OR STRUCTURES ARE |
| | SUPPLIED FROM A COMMON AC SERVICE BY A |
| | FEEDER(S) OR BRANCH CIRCUIT(S), THE |
| | GROUNDING ELECTRODE(S) REQUIRED IN PART |
| | III OF THIS ARTICLE AT EACH BUILDING OR |
| | STRUCTURE SHALL BE CONNECTED IN THE |
| | MANNER SPECIFIED IN 250.32(B) OR (C). |
| | WHERE THERE ARE NO EXISTING GROUNDING |
| | ELECTRODES, THE GROUNDING ELECTRODE(S) |
| | REQUIRED IN PART III OF THIS ARTICLE |
| | SHALL BE INSTALLED. SHOW ON RISER. |
| | |
| | 3} THE FEED FROM PANEL A TO PANEL B IS 3 |
| | #2'S ON THE RISER AND 2 #6'S ON PANEL |
| | SCHEDULE "A", CIRCUITS 11,13. |
| | |
| | 4} THE BATH GFI (RM 107), IS ON CIRCUIT |
| | "A 16", WHICH IS SHARED BY OUTSIDE |
| | RECEPTACLES INVIOLATION OF |
| | 210.11(C)(3)-BATH CIRCUITS. |
| | |
| | 5} THE RECEPTACLE IN THE KITCHEN ON |
| | CIRCUIT "A28" SHOULD BE ON A SMALL |
| | APPLIANCE CIRCUIT PER 210.52(B)(1). |
| | |
| | 6} BEDROOM #2 NEEDS 2 ADDED RECEPTACLES |
| | TO COMPLY WITH 210.52(A)(2). SEE |
| | REVIEWED SET. |
| | |
| | 7} THE JACUZZI MUST BE GFI PROTECTED PER |
| | 680.44. |
| | |
| | REGARDING THE APARTMENTS IN THE SEPARATE |
| | STRUCTURE: SHEET"E-3". |
| | |
| | 1} THE SMOKE DETECTORS MUST BE ON ARC |
| | FAULT PROTECTED. ALSO NOTE THAT THE |
| | FIRST FLOOR DETECTORS ARE ON THE SECOND |
| | FLOOR PANEL. |
| | |
| | 2} THE UPPER BATH CIRCUIT MUST COMPLY |
| | WITH 210.11(C)(3). SEE CIRCUIT # D-18 |
| | FEEDS THE SMOKE DETECTORS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |